Assessment of PMU-based wide-area angle criterion for fault detection in microgrid

被引:31
|
作者
Sharma, Nikhil Kumar [1 ]
Samantaray, Subhransu Ranjan [1 ]
机构
[1] Indian Inst Technol, Sch Elect Sci, Bhubaneswar, India
关键词
distributed power generation; fault diagnosis; synchronisation; phasor measurement; power system measurement; power distribution faults; power distribution system; serious protection challenges; effective fault detection scheme; reliable fault detection scheme; present-day microgrid environment; phasor measurement unit-based wide-area phase angle criterion; protection system; voltage phase angle difference; fault point; accurate measurement; faithful measurement; faulted conditions; phasor data concentrator; time synchronised phasor data; protection index; effective fault detection measure; microgrid including large variations; PMU-based wide-area angle criterion; distributed generation; DISTRIBUTION NETWORKS; DISTRIBUTION-SYSTEMS; PROTECTION SCHEME; SYNCHROPHASORS;
D O I
10.1049/iet-gtd.2019.0027
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The penetration of distributed generation in the power distribution system has increased significantly in recent years, bringing serious protection challenges. Hence, it is mandated to develop effective and reliable fault detection scheme for present-day microgrid environment. This study presents a phasor measurement unit-based (PMU) wide-area phase angle criterion for building a protection system for the microgrid. The absolute value of the rate of change of voltage phase angle difference between the point of common coupling and the bus closest to the fault point is utilised for fault detection in grid connected as well as in the islanded modes of operation. C37.118.1 complied PMUs are employed at the appropriate locations for accurate and faithful measurement of voltage phase angle and the rate of angle difference (RAD) for detecting faulted conditions. PMUs are connected to phasor data concentrator, which receives the time synchronised phasor data and acts as a centralised processing unit. The proposed protection index has been extensively validated on MATLAB/Simulink environment as well as the real-time digital simulator with external PMUs. The test results show that the proposed RAD is a potential candidate for providing effective fault detection measure for microgrid including large variations in operating conditions.
引用
收藏
页码:4301 / 4310
页数:10
相关论文
共 50 条
  • [41] Review of PMU-based Online Applications for Dynamic Simulation, Fault Detection, and Cascading Failure Prevention
    Chen, Zhe
    Li, Fangxing
    Fan, Lingling
    Zhang, Pei
    PROCEEDINGS OF THE 8TH WSEAS INTERNATIONAL CONFERENCE ON ELECTRIC POWER SYSTEMS, HIGH VOLTAGES, ELECTRIC MACHINES, 2008, : 212 - 216
  • [42] Probability Estimation for the Fault Detection and Isolation of PMU-Based Transmission Line System of Smart Grid
    Naseem, Syed Atif
    Eslampanah, Raheleh
    Uddin, Riaz
    2018 5TH INTERNATIONAL CONFERENCE ON ELECTRICAL AND ELECTRONIC ENGINEERING (ICEEE), 2018, : 284 - 288
  • [43] Real-Time Wide-Area Fault Locator for Power Transmission Networks Using Sparse PMU Measurements
    Guha, Bikiran
    Flueck, Alexander J.
    2020 IEEE POWER & ENERGY SOCIETY INNOVATIVE SMART GRID TECHNOLOGIES CONFERENCE (ISGT), 2020,
  • [44] Fault tolerant wide-area parallel computing
    Weissman, JB
    PARALLEL AND DISTRIBUTED PROCESSING, PROCEEDINGS, 2000, 1800 : 1214 - 1225
  • [45] Malicious Corruption Resilience in PMU Data and Wide-Area Damping Control
    Mahapatra, Kaveri
    Ashour, Mahmoud
    Chaudhuri, Nilanjan Ray
    Lagoa, Constantino M.
    IEEE TRANSACTIONS ON SMART GRID, 2020, 11 (02) : 958 - 967
  • [46] Customizable fault tolerance for wide-area replication
    Amir, Yair
    Coan, Brian
    Kirsch, Jonathan
    Lane, John
    SRDS 2007: 26TH IEEE INTERNATIONAL SYMPOSIUM ON RELIABLE DISTRIBUTED SYSTEMS, PROCEEDINGS, 2007, : 66 - +
  • [47] Interpretation and visualization of wide-area PMU measurements using Hilbert analysis
    Messina, A. R.
    Vittal, Vijay
    Ruiz-Vega, Daniel
    Enriquez-Harper, G.
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (04) : 1763 - 1771
  • [48] A new PMU-based fault location algorithm for three-terminal
    Shen Hong-yu
    Zhang Wen-jun
    Duan Yu-bo
    Xu Jian-jun
    ADVANCES IN CHEMICAL, MATERIAL AND METALLURGICAL ENGINEERING, PTS 1-5, 2013, 634-638 : 3925 - 3929
  • [49] New wide-area algorithms for detection and mitigation of angle instability using synchrophasors
    Hu, Dongchen
    Venkatasubramanian, Vaithianathan Mani
    2007 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-10, 2007, : 2182 - +
  • [50] A new PMU-based fault location algorithm for series compensated lines
    Yu, CS
    Liu, CW
    Yu, SL
    Jiang, JA
    IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (01) : 33 - 46