Effects of instrument transformers connection point on measured impedance by distance relay in presence of SSSC

被引:0
作者
Kazemi, A. [1 ]
Jamali, S. [1 ]
Shateri, H. [1 ]
机构
[1] Iran Univ Sci & Technol, Ctr Excellence Power Syst Automat & Operat, Dept Elect Engn, Tehran 16846, Iran
来源
2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6 | 2006年
关键词
distance protection; fault resistance; FACTS devices; tripping characteristic; SSSC;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the measured impedance at the relaying point in the presence of a series connected Flexible Alternating Current Transmission System (FACTS) device, i.e. Static Synchronous Series Compensator (SSSC). The presence of SSSC on a transmission line has a great influence on the tripping characteristic of distance relays. Distance relay tripping characteristic itself depends on the power system structural conditions (short circuit levels at the fine ends), pre-fault operational conditions (load angle and voltage magnitude ratio at the line ends), and especially the ground fault resistance. In the presence of SSSC, its controlling parameters as well as the connection point of the instrument transformers of distance relay affect the tripping characteristic. Here, the measured impedance at the relaying point is calculated due to concerning parameters.
引用
收藏
页码:2467 / 2472
页数:6
相关论文
共 9 条
  • [1] Adaptive relay setting for flexible AC transmission systems (FACTS)
    Dash, PK
    Pradhan, AK
    Panda, G
    Liew, AC
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (01) : 38 - 43
  • [2] DASH PK, P 2000 IEEE POW ENG, V3, P1967
  • [3] DOMMEL HW, 1997, MICROTRAN POWER SYST
  • [4] FAN D, P 2002 IEEE INT C PO, V4, P2608
  • [5] JAMALI S, P 2001 IEE 7 INT C D, P149
  • [6] JAMALI S, P 2004 IEEE INT C PO, P1833
  • [7] JOHNS AT, 1999, FLEXIBLE TRANSMISSIO
  • [8] XIA YQ, 1994, IEEE T POWER DELIVER, V9, P480, DOI 10.1109/61.277720
  • [9] ZHIZHE Z, 1991, IEEE T POWER DELIVER, V6, P135