An application of conventional and advanced exergy approaches on a R41/R1233ZD(E) cascade refrigeration system under optimum conditions

被引:4
作者
Aktemur, Cenker [1 ]
Hacipasaoglu, Servet Giray [1 ]
机构
[1] Kocaeli Univ, Dept Mech Engn, Umuttepe Campus, TR-41380 Kocaeli, Turkey
来源
JOURNAL OF THERMAL ENGINEERING | 2022年 / 8卷 / 02期
关键词
Cascade Refrigeration System; Advanced Exergy Analysis; Conventional Exergy Analysis; R41; R1233zd(E); THERMODYNAMIC ANALYSIS; GWP REFRIGERANTS; PERFORMANCE; ENERGY; CYCLE; CO2; TEMPERATURE; R1233ZD(E); UNDERSTAND; PARALLEL;
D O I
10.18186/thermal.1080196
中图分类号
O414.1 [热力学];
学科分类号
摘要
Painstaking adjustment of an optimum low-temperature cycle (LTC) condenser temperature allows cascade refrigeration system (CRS) to operate at maximum performance. This study exhibits an original approach because, for the first time, advanced exergy analysis is implemented under an optimum LTC condenser temperature of CRS operating with R41/R1233zd(E) as an environmentally-friendly refrigerant pair. Under the auspices of advanced exergy analysis, there is endogenous exergy destruction of 50.43% and exogenous exergy destruction of 49.57% within total exergy destruction. It is pointed out that the interactions between the CRS components (external irreversibilities) are partly less than exergy destruction that occurs within components (internal irreversibilities). The avoidable part within total exergy destruction, which is greater than the unavoidable part, indicates that components have a high improvement potential with a value of 56.31%. Furthermore, LTC compressor depends significantly on other components, as it has the largest exogenous part of exergy destruction with 75.82%. The results indicate that the CRS's exergy efficiency, which can be determined based on conventional exergy analysis, is only 36%. However, this increases to 68% with the improvements needed for the components.
引用
收藏
页码:182 / 201
页数:20
相关论文
共 65 条
[1]  
Acikkalp E, 2015, 20 C THERM SCI TECHN, P1
[2]   Experimental evaluation of a cascade refrigeration system prototype with CO2 and NH3 for freezing process applications [J].
Alberto Dopazo, J. ;
Fernandez-Seara, Jose .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (01) :257-267
[3]  
Aman J, 2018, P CA SOC MECH ENG IN, P1
[4]   Advanced exergy analysis on a modified auto-cascade freezer cycle with an ejector [J].
Bai, Tao ;
Yu, Jianlin ;
Yan, Gang .
ENERGY, 2016, 113 :385-398
[5]   Advanced exergy analyses of an ejector expansion transcritical CO2 refrigeration system [J].
Bai, Tao ;
Yu, Jianlin ;
Yan, Gang .
ENERGY CONVERSION AND MANAGEMENT, 2016, 126 :850-861
[6]   Energetic and exergetic analyses of T56 turboprop engine [J].
Balli, Ozgur ;
Hepbasli, Arif .
ENERGY CONVERSION AND MANAGEMENT, 2013, 73 :106-120
[7]   A Theoretical Comparative Study of CO2 Cascade Refrigeration Systems [J].
Bellos, Evangelos ;
Tzivanidis, Christos .
APPLIED SCIENCES-BASEL, 2019, 9 (04)
[8]   Refrigerants and their environmental impact Substitution of hydro chlorofluorocarbon HCFC and HFC hydro fluorocarbon. Search for an adequate refrigerant [J].
Benhadid-Dib, Samira ;
Benzaoui, Ahmed .
TERRAGREEN 2012: CLEAN ENERGY SOLUTIONS FOR SUSTAINABLE ENVIRONMENT (CESSE), 2012, 18 :807-816
[9]   Thermodynamic analysis and optimization of a novel N2O-CO2 cascade system for refrigeration and heating [J].
Bhattacharyya, Souvik ;
Garai, Anirban ;
Sarkar, Jahar .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (05) :1077-1084
[10]   Ozone depletion and global warming: Case for the use of natural refrigerant - a review [J].
Bolaji, B. O. ;
Huan, Z. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 18 :49-54