Stability of mineral oil and oil-ester mixtures under thermal ageing and electrical discharges

被引:35
作者
Hamdi, Ahmed [1 ]
Fofana, Issouf [2 ]
Djillali, Mahi [1 ]
机构
[1] Univ Laghouat, Semicond & Dielectr Mat Lab, POB 37 G,Ghardaia Rd, Laghouat 03000, Algeria
[2] Univ Quebec Chicoutimi, Res Chair Aging Power Network Infrastruct ViAHT, Chicoutimi, PQ, Canada
关键词
ageing; discharges (electric); mixtures; insulating oils; turbidity; standards; cost reduction; mineral oil stability; oil-ester mixtures; thermal ageing; electrical discharges; mineral-based oil mixtures; dissolved decay products; dielectric dissipation factor; ASTM standards; hydrocarbon blend; oil gassing; synthetic esters; POWER; FLUIDS;
D O I
10.1049/iet-gtd.2016.1970
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This study summarises the results of an experimental investigation on the stability of mineral-based oil mixtures when they are confronted with different ratios of synthetic ester under conditions of electrical discharge, electrical breakdown and a combination of both. The condition of the oil samples was assessed using diagnostic techniques such as gassing tendency, turbidity, dissolved decay products (DDP) and dielectric dissipation factor (DDF), according to ASTM standards. A comparison is made between the performances of fresh and aged samples. The results provide experimental evidence that the chemical composition of hydrocarbon blend is contributing factors to oil gassing. It was observed that aged oils release more gases than new one. It was also observed that the gassing tendency increased with increasing amount of ester for the mixed fluids. The pressure and the absorbance of gases vary proportionally with ester content. Under thermal stress, an increase in pressure is observed especially for the mineral oil sample. The turbidity, DDP and DDF measurements revealed higher values for mineral oil. Importantly, the stability improved with increasing ester content in the blends. Mixed mineral oil/ester therefore offers many advantages with concomitant cost reductions compared with pure synthetic esters.
引用
收藏
页码:2384 / 2392
页数:9
相关论文
共 27 条
[1]  
[Anonymous], 6181 ASTM, V10. 03
[2]  
[Anonymous], 2008, 92408 ASTM, V10. 03
[3]  
[Anonymous], 2002, 87702 ASTM
[4]  
[Anonymous], 2008, 6180 ASTM, V10. 03
[5]  
[Anonymous], 2011, 2011 IEEE C DIEL LIQ, DOI [10. 1109/icdl. 2011. 6015484, DOI 10.1109/ICDL.2011.6015484]
[6]  
[Anonymous], 2005, 193495 ASTM, V10. 03
[7]  
[Anonymous], 2010, 680202 ASTM, V10. 03
[8]  
Berger N., 2002, INSULATING FLUIDS D, V2470
[9]   Comparative evaluation of alternative fluids for power transformers [J].
Fernandez, Inmaculada ;
Ortiz, Alfredo ;
Delgado, Fernando ;
Renedo, Carlos ;
Perez, Severiano .
ELECTRIC POWER SYSTEMS RESEARCH, 2013, 98 :58-69
[10]   Characterization of aging transformer oil-pressboard insulation using some modern diagnostic techniques [J].
Fofana, I. ;
Bouaicha, A. ;
Farzaneh, M. .
EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2011, 21 (01) :1110-1127