Effect of Material Volume Conductivity on Surface Charges Accumulation on Spacers under DC Electro-Thermal Coupling Stress

被引:41
作者
Ma, Guo-ming [1 ]
Zhou, Hong-yang [1 ]
Lu, Shi-Jie [1 ]
Wang, Yuan [1 ]
Liu, Shu-pin [1 ]
Li, Cheng-rong [1 ]
Tu, You-Ping [1 ]
机构
[1] North China Elect Power Univ, Beijing Key Lab High Voltage & EMC, Key Lab Alternate Elect Power Syst Renewable Ener, Beinong Rd 2, Beijing 102206, Peoples R China
关键词
cone-type spacer; DC GIL; surface charge; thermal stress; volume conductivity; INSULATION; GIS; TEMPERATURE; PREDICTION; VOLTAGES; SYSTEMS;
D O I
10.1109/TDEI.2018.007140
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The modification of insulating materials is regarded as an important way to improve the insulation performance of DC spacers. Many simulations have been carried out to guide the development of insulating materials. However, the impacts of temperature on surface charge accumulation and electric field distributions are neglected in many simulations. Since the conductivities are strongly impacted by temperature, the thermal stresses should be considered in the simulations of charge accumulation. To solve these problems, a coupled electro-thermal field simulation model of charge accumulation under DC stress is proposed in this paper. Then, a DC spacer model is introduced as an example, and the parameters in the simulation are shown. Based on the simulation model, the effects of the spacer volume conductivity on the distribution of the surface charge, the saturation time of charge accumulation and the distribution of the electric field along the spacer are investigated. In addition, the influencing mechanism is explained. The results indicate that the volume conductivity of the insulating material should be decreased by two orders of magnitude from the existing AC materials to reduce the surface charge accumulation. With the reduced volume conductivity, 1) the peak value of the charge density on the upper surface decreases 52.9%, and that of lower surface decreases 51.0%; 2) the peak value of the tangential component of the electric field strength along the cone-type spacer in DC-GIL decreases by 12.2%; and 3) the duration of the capacitive-resistive field transition increases by 38.5-fold. The simulation method and advice on the material volume conductivity can be referenced in the DC space design.
引用
收藏
页码:1211 / 1220
页数:10
相关论文
共 24 条
[1]  
[Anonymous], 1983, MITSUBISHI DENKI GIH, V57, P4
[2]  
Christen T, 2013, IEEE INT C SOL DIEL, P238, DOI 10.1109/ICSD.2013.6619804
[3]   Providing all global energy with wind, water, and solar power, Part II: Reliability, system and transmission costs, and policies [J].
Delucchi, Mark A. ;
Jacobson, Mark Z. .
ENERGY POLICY, 2011, 39 (03) :1170-1190
[4]   MECHANISM AND EFFECT OF DC CHARGE ACCUMULATION ON SF6 GAS INSULATED SPACERS [J].
FUJINAMI, H ;
TAKUMA, T ;
YASHIMA, M ;
KAWAMOTO, T .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (03) :1765-1772
[5]  
Gremaud R., 2016, SOLID GAS INSULATION
[6]  
Gremaud R., 2014, CIGRE SESS PAR
[7]  
Guru B S, 2004, ELECTROMAGNETIC FIEL, V36, P914
[8]   Development of insulation structure and enhancement of insulation reliability of 500 kV dc GIS [J].
Hasegawa, T ;
Yamaji, K ;
Hatano, M ;
Endo, F ;
Rokunohe, T ;
Yamagiwa, T .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :194-202
[9]  
Kim JK, 2005, IEEE T MAGN, V41, P1636, DOI [10.1106/TMAG.2005.846117, 10.1109/TMAG.2005.846117]
[10]  
Koch H., 2011, GAS INSULATED TRANSM