摘要
This paper analyzes the use of the voltage distortions in PWM voltage-source-inverters (VSIs) caused by the non-ideal behavior of the inverter for islanding detection purposes. The non-ideal characteristic of the inverters, mainly due to the dead-time needed to have safe commutations, produces fundamental frequency dependent harmonics (-5th, 7th...) in the output voltage. Although these harmonics are in principle an unwanted effect, since they reduce the power quality, they can potentially be used for islanding detection purposes. The physical principles of the method would be the same as for high frequency signal injection methods that have already been proposed but without the need of injecting a high frequency signal.
引用
收藏
页码:2649 / 2656
页数:8
相关论文
共 29 条
  • [1] [Anonymous], 2000, 9292000 IEEE
  • [2] [Anonymous], 12 VDE
  • [3] [Anonymous], AS4777
  • [4] [Anonymous], 2003, IEEE STANDARD 1547
  • [5] [Anonymous], 2002 IEEE POW ENG SO
  • [6] [Anonymous], 2004, 61727 IEC
  • [7] [Anonymous], P IEEE INT S IND EL
  • [8] [Anonymous], DK 5940 CRIT CONN GE
  • [9] [Anonymous], 1999, UL1741
  • [10] [Anonymous], 2000, 9292000 IEEE