Long-term evaluation of HVDC transmission line audible noise and its correlation with background noise

被引:7
|
作者
Shin, Koo Yong [1 ]
Oh, Joon Arm [1 ]
Kwon, Gu Min [1 ]
Ju, Mun No [2 ]
Woo, Jeong Min [2 ]
机构
[1] Korea Elect Power Corp KEPCO, KEPRI, Daejeon 34056, South Korea
[2] Korea Electrotechnol Res Inst, Elect Environm Res Ctr, Chang Won 51543, South Korea
来源
AIP ADVANCES | 2019年 / 9卷 / 09期
关键词
ION-FLOW-FIELD; CORONA PERFORMANCE;
D O I
10.1063/1.5111434
中图分类号
TB3 [工程材料学];
学科分类号
0805 ; 080502 ;
摘要
The audible noise (AN) generated by corona discharge from a full-scale, high-voltage direct-current (HVDC) transmission line was evaluated over a one-year period from December 2017 to November 2018. The double bipolar HVDC transmission line using a metallic return conductor was demonstrated using a full-scale tower having a height of 21 m in Gochang, Korea. The measured AN in an outdoor environment was statistically evaluated and compared in different seasons and weather conditions. The A-weighted spectrum of the HVDC corona noise exhibited a greater distribution than the background noise above 1.0 kHz in the frequency domain. Various background noises were considered and eliminated to improve the measurement accuracy. The highest AN levels were exhibited during the spring season. Individuals in the age range of 18-60 years were randomly selected to conduct a human-perception test. The results indicated that 15% of the participants became aware of the AN from the corona discharge when it was >5 dBA greater than the background noise. The AN was <36 dBA when the conductor surface gradient was <18 kV/cm with a six-bundle sub-conductor.
引用
收藏
页数:8
相关论文
共 50 条
  • [1] Research on the correlation between corona current spectrum and audible noise spectrum of HVDC transmission line
    Liu, Yingyi
    Zhou, Lijuan
    Liu, Yuanqing
    Yuan, Haiwen
    Ji, Liang
    PHYSICS OF PLASMAS, 2017, 24 (11)
  • [2] Statistical Evaluation and Prediction of Audible Noise of HVDC Transmission Lines
    Yi, Yong
    Chen, Zhengying
    Wang, Liming
    2016 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP), 2016, : 279 - 282
  • [3] LONG-TERM AUDIBLE NOISE AND RADIO NOISE PERFORMANCE FROM AN OPERATING 400-KV TRANSMISSION-LINE
    LARSSON, C
    HALLBERG, B
    ISRAELSSON, S
    IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) : 1842 - 1846
  • [4] The Influence of Wind on the Audible Noise of Ultra HVDC Transmission Line in High Altitude Area
    Li, Min
    Zeng, Rong
    Yang, Dawei
    Yu, Zhanqing
    Li, Ruihai
    Liu, Lei
    Zhang, Bo
    Zhang, Huaying
    2010 ASIA-PACIFIC INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY & TECHNICAL EXHIBITION ON EMC RF/MICROWAVE MEASUREMENTS & INSTRUMENTATION, 2010, : 1668 - 1671
  • [5] Availability of corona cage for predicting audible noise generated from HVDC transmission line
    Nakano, Yukio
    Sunaga, Yoshitaka
    IEEE Transactions on Power Delivery, 1992, v (0n) : 1422 - 1431
  • [6] Extract Study of Transmission Line Audible Noise
    Wu Fa-yuan
    Zhou Jin-quan
    Liu Sheng-nan
    Dai Xiao-min
    Liu Ping
    Cai Jun
    2018 3RD INTERNATIONAL CONFERENCE ON SMART CITY AND SYSTEMS ENGINEERING (ICSCSE), 2018, : 439 - 442
  • [7] STATISTICAL AUDIBLE NOISE PERFORMANCE OF SHIOBARA HVDC TEST LINE
    NAKANO, Y
    FUKUSHIMA, M
    IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (01) : 290 - 296
  • [8] The Altitude Effect and Correction of Audible Noise for HVdc Transmission Lines
    Zhao, Luxing
    Lu, Jiayu
    Cui, Xiang
    Xie, Li
    Ju, Yong
    He, Kun
    IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (04) : 1954 - 1963
  • [9] AVAILABILITY OF CORONA CAGE FOR PREDICTING AUDIBLE NOISE GENERATED FROM HVDC TRANSMISSION-LINE
    NAKANO, Y
    SUNAGA, Y
    IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (02) : 1422 - 1431