Are harmonic recommendations according to IEEE and IEC too restrictive?

被引:37
作者
Fuchs, EF [1 ]
Roesler, DJ
Masoum, MAS
机构
[1] Univ Colorado, Dept Elect & Comp Engn, Boulder, CO 80409 USA
[2] Dept Energy, Washington, DC 20585 USA
[3] Iran Univ Sci & Technol, Dept Elect Engn, Tehran 16844, Iran
关键词
flexible limits for voltage/current harmonics; IEEE and IEC harmonic standards; strict limits for sub- and inter-harmonics;
D O I
10.1109/TPWRD.2003.822538
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Experimental and analytical studies of the effects of voltage and current harmonies on induction machines, transformers, appliances, and relays show that the present versions of IEEE and IEC are too restrictive for low-frequency voltage and current (integer) harmonies, as they apply to residential power systems. It is recommended that not rigid but flexible guidelines are established so that different harmonic spectra are permitted which result in the same additional temperature rise in transformers and induction machines. Very restrictive amplitude limits for inter-harmonics and subharmonics should be included in the revision of the above standards due to their detrimental' effects on under-frequency relays (malfunctioning), lighting equipment (flicker) and rotating machines (harmonic torques).
引用
收藏
页码:1775 / 1786
页数:12
相关论文
共 20 条
[1]  
ALASHHAB FS, 1981, THESIS U COLORADO BO
[2]  
[Anonymous], 6100032 IEC
[3]  
[Anonymous], 1992, IEEE519
[4]  
[Anonymous], 182002 IEEE
[5]  
*ANSI IEEE, 1986, 141 ANSIIEEE
[6]  
*ANSI IEEE, 1998, C57110D7 ANSIIEEE
[7]  
de Abreu JPG, 2000, INT C HARMON QUAL PO, P251, DOI 10.1109/ICHQP.2000.897033
[8]  
Fuchs E. F., 1982, Reliability in Electrical and Electronic Components and Systems. Fifth European Conference on Electrotechnics - EUROCON '82, P591
[9]   AGING OF ELECTRICAL APPLIANCES DUE TO HARMONICS OF THE POWER-SYSTEMS VOLTAGE [J].
FUCHS, EF ;
ROESLER, DJ ;
KOVACS, KP .
IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (03) :301-307
[10]   Measurement of Eddy-current loss coefficient PEC-R, derating of single-phase transformers, and comparison with K-factor approach [J].
Fuchs, EF ;
Yildirim, D ;
Grady, WM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (01) :148-154