Voltage Sag Detection in Grid-connected Photovoltaic Power Plant for Low Voltage Ride-through Control

被引:5
作者
Al-Shetwi, Ali Qasem [1 ]
Sujod, Muhamad Zahim [1 ]
机构
[1] Univ Malaysia Pahang, Dept Elect & Elect Engn, Pahang 26600, Pekan, Malaysia
关键词
Photovoltaic power plant; sag detection; grid faults; low voltage-ride through; PV inverter; grid codes; FAULT-DETECTION; INTEGRATION; REQUIREMENTS; DESIGN;
D O I
10.2174/2352096511666180626151223
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Background: Due to the high level of photovoltaic power plants (PVPPs) penetration into power grids, disconnections of these plants during faults are no longer possible as it may cause problems concerning stability, quality, and operation of the power system. Therefore, new grid codes have been established with low voltage ride-through (LVRT) capability standard requirements for grid-connected PVPPs that should be met. Therefore, for an efficient LVRT control, the fast and precise sag detection strategy is essential for the system to switch from normal operation to LVRT mode of operation. Methods: For this purpose, this paper presents a two automatic fault detection methods which are RMS-based (d-q) components of grid voltage and positive sequence voltage. These methods were utilized to determine the beginning and end of a voltage sag and to determine the sag depth to regulate the required reactive current that should be injected according to the LVRT standard requirements. The operating method depends on calculating present grid voltage under faults to the nominal voltage that identifies the sags' depth and therefore inject the required amount of reactive power accordingly. Also, a comparison between the two proposed methods regarding response speed and accuracy was made. The effectiveness of these detection strategies is that it can be integrated into the voltage source inverter (VSI) without utilizing additional external hardware or software programming. Results: The simulation results demonstrated a good precision and how straightforward the proposed methods' usage is, proving that the RMS method is faster and more accurate than positive sequence method. Conclusion: In conclusion, it was found that RMS detection algorithm is preferred for a more accurate and efficient LVRT control.
引用
收藏
页码:384 / 392
页数:9
相关论文
共 25 条
[1]  
Al-Shetwi A. Q., 2015, ARPN J. Eng. Appl. Sci., V10, P9906
[2]  
Al-Shetwi A. Q., 2016, NAT C POSTGR RES NCO, P193
[3]  
Al-Shetwi A. Q., 2016, INT J RENEWABLE ENER, V6, P1442, DOI DOI 10.1234/ijrer.v6i1.3212.g6785
[4]   Grid-connected photovoltaic power plants: A review of the recent integration requirements in modern grid codes [J].
Al-Shetwi, Ali Q. ;
Sujod, Muhamad Zahim .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2018, 42 (05) :1849-1865
[5]   Modeling and Control of Grid-Connected Photovoltaic Power Plant With Fault Ride-Through Capability [J].
Al-Shetwi, Ali Q. ;
Sujod, Muhamad Zahim .
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 2018, 140 (02)
[6]   Low voltage ride-through capability control for single-stage inverter-based grid-connected photovoltaic power plant [J].
Al-Shetwi, Ali Q. ;
Sujod, Muhamad Zahim ;
Blaabjerg, Frede .
SOLAR ENERGY, 2018, 159 :665-681
[7]  
Al-Shetwi AQ, 2016, 2016 INTERNATIONAL CONFERENCE ON ADVANCES IN ELECTRICAL, ELECTRONIC AND SYSTEMS ENGINEERING (ICAEES), P488, DOI 10.1109/ICAEES.2016.7888094
[8]   Analysis of Voltage Sag Severity Case Study in an Industrial Circuit [J].
Arias-Guzman, Santiago ;
Andres Ruiz-Guzman, Oscar ;
Felipe Garcia-Arias, Luis ;
Jaramillo-Gonzales, Maria ;
Daniel Cardona-Orozco, Pablo ;
Ustariz-Farfan, Armando J. ;
Cano-Plata, Eduardo A. ;
Felipe Salazar-Jimenez, Andres .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2017, 53 (01) :15-21
[9]   Review of advanced grid requirements for the integration of large scale photovoltaic power plants in the transmission system [J].
Cabrera-Tobar, Ana ;
Bullich-Massague, Eduard ;
Aragues-Penalba, Monica ;
Gomis-Bellmunt, Oriol .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 62 :971-987
[10]   Faulty PV panel identification using the Design of Experiments (DoE) method [J].
Charles, J. -P. ;
Hannane, F. ;
El-Mossaoui, H. ;
Zegaoui, A. ;
Nguyen, T. V. ;
Petit, P. ;
Aillerie, M. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 57 :31-38