Dynamic heating control measured and simulated effects on power reduction, energy and indoor air temperature in an old apartment building with district heating

被引:8
作者
Hajian, Hatef [1 ]
Ahmed, Kaiser [1 ]
Kurnitski, Jarek [1 ,2 ]
机构
[1] Aalto Univ, Dept Civil Engn, Espoo 02150, Finland
[2] Tallinn Univ Technol, FinEst Ctr Smart Cities, Finest Ctr, EE-19086 Tallinn, Estonia
基金
芬兰科学院;
关键词
Space heating; Heating power; Power reduction; Heating curve; Dynamic control; Central heating;
D O I
10.1016/j.enbuild.2022.112174
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study investigated the effects of the dynamic heating control on power reduction and indoor air temperature in a typical Finnish block of apartments built in 1981. The building operated in 2018 with conventional and in 2020 with dynamic heating control. The onsite measured data was collected from both periods. Measured data enabled calibrating the whole building simulation models with an accuracy better than 10%. A new dynamic heating curve control algorithm was developed so that outdoor air compensated supply temperature was reduced during high use of Domestic Hot Water (DHW) by applying DHW compensation differential. If the indoor air temperature in any apartment dropped below the limit, supply temperature uplift was applied. The dynamic heating control resulted in 8.9% space heating and 13.7% total heating power reduction while had practically no effect on energy use. On the contrary, dynamic heating control slightly increased indoor temperature fluctuations, but both control systems resulted in a similar value of hours below the setpoint temperature of 21 degrees C. The results demonstrate that heating power reduction without compromising indoor air temperature is possible with applied supply temperature drop during DHW peaks and preheating afterwards. (c) 2022 Published by Elsevier B.V.
引用
收藏
页数:12
相关论文
共 33 条
[1]   Hourly consumption profiles of domestic hot water for different occupant groups in dwellings [J].
Ahmed, Kaiser ;
Pylsy, Petri ;
Kurnitski, Jarek .
SOLAR ENERGY, 2016, 137 :516-530
[2]  
[Anonymous], AIVC AIR INFILTRATIO
[3]  
[Anonymous], BUILDING OWNERS LEAN
[4]  
[Anonymous], STAT FINLAND ENERGY
[5]  
[Anonymous], 2017, 177721 ISO
[6]  
[Anonymous], 2017, National building code of Finland (Suomen saadoskokoelma)
[7]  
[Anonymous], HOME FINNISH METEORO
[8]  
*AUT, 2020, REV BIM SOFTW AUT OF, P1
[9]   Improved Control of Radiator Heating Systems with Thermostatic Radiator Valves without Pre-Setting Function [J].
Benakopoulos, Theofanis ;
Salenbien, Robbe ;
Vanhoudt, Dirk ;
Svendsen, Svend .
ENERGIES, 2019, 12 (17)
[10]  
Bosseboeuf, 2015, ENERGY EFFICIENCY TR, P97