Advanced common control method for shunt and series active compensators used in power quality improvement

被引:16
作者
Alali, MAE [1 ]
Chapuis, YA
Saadate, S
Braun, F
机构
[1] Univ Aleppo, Fac Elect Engn, Aleppo, Syria
[2] LEPSI 23, F-67037 Strasbourg 2, France
[3] France Univ, GREEN, F-54500 Vandoeuvre Les Nancy, France
来源
IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS | 2004年 / 151卷 / 06期
关键词
D O I
10.1049/ip-epa:20040679
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An advanced common control method for shunt and series active conditioners, which compensate for the main types of disturbances in electrical power systems, is considered. If shunt and series actives conditioners are already well known as good compensation solutions for power quality improvement, it is also admitted that they generate some undesired components at switching frequency. To avoid these propagation problems, conditioner designers proposed a high-order output filter associated to a specific controller based on the RST control method. However, by applying this controller, it can be observed that a phase lag between the reference and the injected signal appears in the current and voltage control loop, which damages harmonic compensation. Therefore, a new RST controller is proposed, called RSTimp, to overcome the phase lag effects over the entire bandwidth for both active conditioners. The RSTimp proposed control method is validated through SABER simulations. These simulations show very good active conditioner performance in terms of rapidity, tracking and robustness for both current and voltage compensation.
引用
收藏
页码:658 / 665
页数:8
相关论文
共 10 条
[1]   New trends in active filters for power conditioning [J].
Akagi, H .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1996, 32 (06) :1312-1322
[2]  
ALALI MAE, 2000, CIEP 2000 AC MEX OCT, P80
[3]  
ALALI MAE, 2001, EPE 2001 AUG GRATZ A
[4]  
ALARCON G, 2000, CIEP 2000 AC MEX OCT, P93
[5]   Compensation of distribution system voltage using DVR [J].
Ghosh, A ;
Ledwich, G .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (04) :1030-1036
[6]   Operation of a phase locked loop system under distorted utility conditions [J].
Kaura, V ;
Blasko, V .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (01) :58-63
[7]  
LAPENA OL, 1999, EPE 99 LAUS SWITZ
[8]   A flexible DSTATCOM operating in voltage or current control mode [J].
Ledwich, G ;
Ghosh, A .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2002, 149 (02) :215-224
[9]  
SANNINO A, 2000, 35 IAS ANN M 2000 IE, P2476
[10]  
VISOSER AJ, 2000, 31 IEEE ANN POW EL S