Forecasting electric demand of supply fan using data mining techniques

被引:22
作者
Le Cam, M. [1 ]
Daoud, A. [2 ]
Zmeureanu, R. [1 ]
机构
[1] Concordia Univ, Dept Bldg Civil & Environm Engn, Ctr Zero Energy Bldg Studies, 1515 St Catherine W, Montreal, PQ H3G 1M8, Canada
[2] Inst Rech Hydro Quebec, Lab Technol Energie, 600 Ave Montagne, Shawinigan, PQ G9N 7N5, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Electric demand; Forecast; Data mining; Building Automation System; Clustering analysis; KNOWLEDGE DISCOVERY; NEURAL-NETWORK; LOAD; OPTIMIZATION; PREDICTION; SELECTION;
D O I
10.1016/j.energy.2016.02.061
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents the application of the process of KDD (knowledge discovery in databases) for the forecasting of the electrical power demand of a supply fan of an AHU (air handling unit). The case study uses trend data from the BAS (Building Automation System), which is recorded every 15 min in an office building. Data mining techniques are used as a preprocessing step in the development of the forecasting model. A clustering analysis detects atypical operations and then partitions the whole dataset into three subsets of typical daily profiles of the supply fan modulation. A hybrid model, combining a closed-loop nonlinear ANN (autoregressive neural network) model and a physical model, forecasts the electric power demand over a horizon of up to 6 h. The optimum architecture of ANN, found by using a Simple Genetic Algorithm, is composed of 13 input neurons, I hidden neuron and 23-day training set size, for the cluster corresponding to working days except Mondays. The results show good agreement between the forecasts and measurements of fan modulation, and electric demand, respectively. The fan modulation was forecasted over the testing period with RMSE (Root Mean Squared Error) of 5.5% and CV(RMSE) of 17.6%. The fan electric demand was forecasted with a RMSE of 1.4 kW, CV(RMSE) of 30% over a 6-h time horizon. The sensitivity analysis indicated that the reduction of training data set size from 23 days to 4 or 8 days does not have a negative impact of the value of RMSE. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:541 / 557
页数:17
相关论文
共 33 条
[1]  
Beale M.H., 2011, NEURAL NETWORK TOOLB
[2]  
Bezdek J. C., 1981, Pattern recognition with fuzzy objective function algorithms
[3]  
Buchheit RB, 2000, INT C COMP CIV BUILD, P914
[4]   Model-based predictive control of an ice storage device in a building cooling system [J].
Candanedo, J. A. ;
Dehkordi, V. R. ;
Stylianou, M. .
APPLIED ENERGY, 2013, 111 :1032-1045
[5]   An adaptive fuzzy combination model based on self-organizing map and support vector regression for electric load forecasting [J].
Che, Jinxing ;
Wang, Jianzhou ;
Wang, Guangfu .
ENERGY, 2012, 37 (01) :657-664
[6]   Artificial Intelligence techniques: An introduction to their use for modelling environmental systems [J].
Chen, Serena H. ;
Jakeman, Anthony J. ;
Norton, John P. .
MATHEMATICS AND COMPUTERS IN SIMULATION, 2008, 78 (2-3) :379-400
[7]  
Chipperfield A., 1994, GENETIC ALGORITHM TO
[8]   Building operation and energy performance: Monitoring, analysis and optimisation toolkit [J].
Costa, Andrea ;
Keane, Marcus M. ;
Torrens, J. Ignacio ;
Corry, Edward .
APPLIED ENERGY, 2013, 101 :310-316
[9]   A Physical Hybrid Artificial Neural Network for Short Term Forecasting of PV Plant Power Output [J].
Dolara, Alberto ;
Grimaccia, Francesco ;
Leva, Sonia ;
Mussetta, Marco ;
Ogliari, Emanuele .
ENERGIES, 2015, 8 (02) :1138-1153
[10]   Fault detection and diagnosis for buildings and HVAC systems using combined neural networks and subtractive clustering analysis [J].
Du, Zhimin ;
Fan, Bo ;
Jin, Xinqiao ;
Chi, Jinlei .