Numerical study on ignition and failure mechanisms of hydrogen explosion accident in Fukushima Daiichi Unit 1

被引:12
作者
Fujisawa, N. [1 ,2 ]
Liu, S. [3 ]
Yamagata, T. [1 ]
机构
[1] Niigata Univ, Fac Engn, Nishi Ku, 8050,Ikarashi 2, Niigata 9502181, Japan
[2] Shinshu Univ, Fac Engn, 4-17-1 Wakasato, Nagano 3808553, Japan
[3] Niigata Univ, Grad Sch Sci & Technol, Nishi Ku, 8050,Ikarashi 2, Niigata 9502181, Japan
关键词
Hydrogen explosion accident; Fukushima Daiichi; Ignition mechanism; Failure mechanism; Numerical analysis;
D O I
10.1016/j.engfailanal.2021.105388
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
This paper studied ignition and failure mechanisms of hydrogen explosion accident in the container building of Fukushima Daiichi Nuclear Power Plant Unit 1, which occurred a day after the Great East Japan Earthquake in 2011. To understand the mechanism of hydrogen explosion, an unsteady three-dimensional numerical analysis of the flow field in the container building was conducted in real time by assuming that the high-temperature hydrogen gas (500 ?C) issued from the head flange of the reactor vessel. The numerical results show that the hydrogen gas spread not only on the 5th floor but also on the 4th floor of the container building covering the stairs. It was found that the hydrogen concentration on the 5th and 4th floors was highly uniform owing to the long real-time accumulation (15 h) of hydrogen, and it spread gradually from the 5th to the 4th floor through the stair. As a result, the hydrogen concentration reached the ignition level on the 4th floor (5%), which could result in the ignition of hydrogen by a tank heater on the 4th floor and the flame propagated to the 5th floor, where fast deflagration and detonation might occur because of the high concentration of hydrogen gas (19%). This scenario is consistent with the observations of failure mechanism after the explosion accident.
引用
收藏
页数:12
相关论文
共 29 条
[1]  
[Anonymous], 2012, FIN REP
[2]  
[Anonymous], 2003, FED REG
[3]   Spontaneous ignition of hydrogen leaks: A review of postulated mechanisms [J].
Astbury, G. R. ;
Hawksworth, S. J. .
INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2007, 32 (13) :2178-2185
[4]   APPLICATION OF COMPUTATIONAL FLUID-DYNAMICS IN ROOM VENTILATION [J].
AWBI, HB .
BUILDING AND ENVIRONMENT, 1989, 24 (01) :73-84
[5]   Flammability of methane, propane, and hydrogen gases [J].
Cashdollar, KL ;
Zlochower, IA ;
Green, GM ;
Thomas, RA ;
Hertzberg, M .
JOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, 2000, 13 (3-5) :327-340
[6]   Explosion modeling and analysis of BP Deepwater Horizon accident [J].
Dadashzadeh, Mohammad ;
Abbassi, Rouzbeh ;
Khan, Faisal ;
Hawboldt, Kelly .
SAFETY SCIENCE, 2013, 57 :150-160
[7]  
Dagdougui H, 2018, HYDROGEN INFRASTRUCTURE FOR ENERGY APPLICATIONS: PRODUCTION, STORAGE, DISTRIBUTION AND SAFETY, P127, DOI 10.1016/B978-0-12-812036-1.00007-X
[8]   Fire and explosion disasters occurred due to the Great East Japan Earthquake (March 11, 2011) [J].
Dobashi, Ritsu .
JOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, 2014, 31 :121-126
[9]   Numerical analysis on the wall-thinning rate of a bent pipe by liquid droplet impingement erosion [J].
Fujisawa, Nobuyuki ;
Wada, Keitaro ;
Yamagata, Takayuki .
ENGINEERING FAILURE ANALYSIS, 2016, 62 :306-315
[10]  
Greene S.R., 1986, 14 WAT REACT SAF INF