Security-Constrained Unit Commitment With AC/DC Transmission Systems

被引:69
作者
Lotfjou, Azim [1 ]
Shahidehpour, Mohammad [1 ]
Fu, Yong [1 ]
Li, Zuyi [1 ]
机构
[1] IIT, Dept Elect & Comp Engn, Chicago, IL 60616 USA
关键词
AC/DC transmission systems; Benders decomposition; current source converters; security-constrained unit commitment; POWER-FLOW; LOAD-FLOW; HVDC TRANSMISSION; CONVERTER; EQUATIONS;
D O I
10.1109/TPWRS.2009.2036486
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the solution to the security-constrained unit commitment (SCUC) problem with a detailed representation of high voltage direct current (DC) transmission system with current source converters (CSCs). The SCUC problem is decomposed into a master problem for solving unit commitment (UC) problem and hourly transmission security check subproblems that evaluate branch flows and bus voltages of integrated AC/DC transmission systems. The solution of the transmission security check subproblem is based on a linear programming (LP) formulation that minimizes AC bus mismatches subject to AC/DC transmission constraints. The final SCUC solution prescribes an economic and secure operation and control strategy for AC/DC transmission systems and coordinates DC power transfers for enhancing the economics and the security of AC transmission systems. Numerical tests illustrate the efficiency of the proposed AC/DC transmission model.
引用
收藏
页码:531 / 542
页数:12
相关论文
共 25 条
[1]   High voltage direct current modelling in optimal power flows [J].
Ambriz-Perez, H. ;
Acha, E. ;
Fuerte-Esquivel, C. R. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2008, 30 (03) :157-168
[2]  
[Anonymous], 1994, POWER SYSTEM STABILI
[3]  
Arrillaga J., 2007, Flexible Power Transmission. The HVDC Options
[4]   INCLUSION OF DC CONVERTER AND TRANSMISSION EQUATIONS DIRECTLY IN A NEWTON POWER FLOW [J].
BRAUNAGEL, DA ;
KRAFT, LA ;
WHYSONG, JL .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1976, 95 (01) :76-88
[5]   NEW, FAST TECHNIQUE FOR LOAD-FLOW SOLUTION OF INTEGRATED MULTI-TERMINAL DC-AC SYSTEMS [J].
ELMARSAFAWY, MM ;
MATHUR, RM .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (01) :246-255
[6]   AC contingency dispatch based on security-constrained unit commitment [J].
Fu, Y ;
Shahidehpour, M ;
Li, ZY .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (02) :897-908
[7]   Security-constrained unit commitment with AC constraints [J].
Fu, Y ;
Shahidehpour, M ;
Li, ZY .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (02) :1001-1013
[8]   Fast SCUC for large-scale power systems [J].
Fu, Yong ;
Shahidehpour, Mohammad .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (04) :2144-2151
[9]   PERFORMANCE AND ECONOMIC COMPARISONS BETWEEN POINT-TO-POINT HVDC TRANSMISSION AND HYBRID BACK-TO-BACK HVDC/AC TRANSMISSION [J].
HAMMAD, AE ;
LONG, WF .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (02) :1137-1144
[10]  
HARVEY S, 2004, INTERNAL NYISO HVDC