Energy saving and thermal comfort interventions based on occupants' needs: A students' residence building case

被引:22
作者
Petidis, Loannis [1 ]
Aryblia, Maria [1 ]
Daras, Tryfon [1 ]
Tsoutsos, Theocharis [1 ]
机构
[1] Tech Univ Crete, Sch Environm Engn, Renewable & Sustainable Energy Syst Lab, Univ Campus, Khania 73100, Crete, Greece
关键词
Energy upgrade; Thermal comfort; nZEB; MEDITERRANEAN HOTELS;
D O I
10.1016/j.enbuild.2018.05.057
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The existing residential building of the Technical University of Crete students has studied as well as the current indoor conditions and the occupants' energy consumption behaviour and satisfaction, in order to identify the proper building interventions. The current energy performance of the building is poor like the majority of the old social buildings in Europe; in the social buildings in Greece, passive solar and cooling principles were not the main priority for the past architects and engineers. The survey highlighted problems such as insufficient lighting (20% use artificial lighting at noon in winter and 24% in the afternoon in summer) and thermal discomfort, especially in winter (only 17,65% were satisfied compared to 37,25% in summer). High values of humidity and insufficient ventilation were also observed. Five scenarios concerning the reduction of energy consumption were chosen towards a nearly zero energy building with a reasonable payback period. The annual dorm building energy consumption is about 70,1 kWh/m(2). The first investigated scenario of thermal insulation on building envelope presents 10% savings leading to a reduced consumption of 63,1 kWh/m(2), while correspondingly the green roof achieved an 1,7% reduction (68,9 kWh/m(2)), LED bulbs 14,6% reduction (59,9 kWh/m(2)) and substitution of windows 17,4% reduction on energy consumption (57,9 kWh/m(2)). The combination scenario includes all the above described interventions summing total savings up to 36% (44,9 kWh/m(2)). Given the newly reduced consumption, the installation of a self-producing PV plant was studied according to three alternative scenarios; achieving 50% of total electricity needs, 100% of total needs and optimal use of freely available roof space. The installation of a PV plant suitable for the available roof space achieved 62% savings compared to initial energy consumption, a very satisfactory result for the target of near-zero energy performance in the dormitory building. (C) 2018 Elsevier B.V. All rights reserved.
引用
收藏
页码:347 / 364
页数:18
相关论文
共 13 条
  • [1] Longitudinal analysis of normative energy use feedback on dormitory occupants
    Anderson, Kyle
    Song, Kwonsik
    Lee, SangHyun
    Krupka, Erin
    Lee, Hyunsoo
    Park, Moonseo
    [J]. APPLIED ENERGY, 2017, 189 : 623 - 639
  • [2] [Anonymous], Energy efficiency in buildings
  • [3] Chung M. H., 2014, ENERGY BUILD, V78, P7, DOI [10.1016/j.enpol.2010.01.009, DOI 10.1016/J.ENPOL.2010.01.009]
  • [4] Sustainable power planning for the island of Crete
    Giatrakos, Georgios P.
    Tsoutsos, Theocharis D.
    Zografakis, Nikos
    [J]. ENERGY POLICY, 2009, 37 (04) : 1222 - 1238
  • [5] Design of large scale prosuming in Universities: The solar energy vision of the TUC campus
    Hasapis, Dimitrios
    Savvakis, Nikolaos
    Tsoutsos, Theocharis
    Kalaitzakis, Konstantinos
    Psychis, Spyridon
    Nikolaidis, Nikolaos P.
    [J]. ENERGY AND BUILDINGS, 2017, 141 : 39 - 55
  • [6] A simulation of the energy consumption monitoring in Mediterranean hotels Application in Greece
    Karagiorgas, Michaelis
    Tsoutsos, Theocharis
    Moia-Pol, A.
    [J]. ENERGY AND BUILDINGS, 2007, 39 (04) : 416 - 426
  • [7] Energy efficiency in the Hellenic building sector: An assessment of the restrictions and perspectives of the market
    Karkanias, C.
    Boemi, S. N.
    Papadopoulos, A. M.
    Tsoutsos, T. D.
    Karagiannidis, A.
    [J]. ENERGY POLICY, 2010, 38 (06) : 2776 - 2784
  • [8] Makridis and Associates, 2014, EN EFF LOW INC HOUS
  • [9] Assessment of fixed shading devices with integrated PV for efficient energy use
    Mandalaki, M.
    Zervas, K.
    Tsoutsos, T.
    Vazakas, A.
    [J]. SOLAR ENERGY, 2012, 86 (09) : 2561 - 2575
  • [10] Simulation Based Analysis on the Energy Conservation Effect of Green Wall Installation for Different Building Types in a Campus
    Poddar, Sinchita
    Park, Dong Yoon
    Chang, Seongju
    [J]. 8TH INTERNATIONAL CONFERENCE ON SUSTAINABILITY IN ENERGY AND BUILDINGS, SEB-16, 2017, 111 : 236 - 244