Evaluation of high-rate clarification for wet-weather-only treatment facilities

被引:10
作者
Jolis, D [1 ]
Ahmad, ML [1 ]
机构
[1] San Francisco Publ Util Commiss, Water Pollut Control Div, San Francisco, CA USA
关键词
ballasted flocculation; combined sewer overflows; high-rate clarification; wet-weather-only treatment facilities;
D O I
10.2175/106143004X151563
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
High-rate clarification (HRC) processes are well suited for enhanced primary treatment of wet-weather flows in combined sewer systems. Suspended solids removal in excess of 75% of influent concentrations can be achieved consistently. Chemical oxygen demand and five-day biochemical oxygen demand removal are better than 60%. However, although optimal treatment could be achieved in a matter of minutes when the units were started full, a delay of up to one-half hour was observed when the units were started empty. Operational strategies that minimize this effect need to be developed in full-scale tests before HRC processes can be implemented with confidence in wet-weather-only facilities.
引用
收藏
页码:474 / 480
页数:7
相关论文
共 7 条
[1]  
*AM PUBL HLTH ASS, 1998, STAND METH EV WAT WA
[2]  
CRUMB SF, 2000, WATER ENV TECHNOL, V12, P41
[3]  
GERRITY D, 1999, P 72 ANN WAT ENV FED
[4]  
*METC EDD INC, 2003, WAST ENG TREATM REUS
[5]  
*NAT SAN FDN INT, 1999, DRAFT VER PROT CHEM
[6]  
STACHOWIAK RG, 1999, P 72 ANN WAT ENV FED
[7]   Factors affecting ballasted flocculation reactions [J].
Young, JC ;
Edwards, FG .