Effect of overhead ground wires on reduction of failure rates of surge arresters on power distribution lines

被引:0
|
作者
Nakada, K [1 ]
Yokota, T
Yokoyama, S
Asakawa, A
Kawabata, T
机构
[1] Cent Res Inst Elect Power Ind, Elect Insulat Dept, Komae Res Lab, Tokyo, Japan
[2] Hokuriku Elect Power Co, Takefu Branch Off, Distribut Maintenance & Operat Sect, Toyama, Japan
关键词
D O I
10.1002/(SICI)1520-6416(19980130)122:2<12::AID-EEJ2>3.0.CO;2-Z
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Surge arresters are sometimes damaged by lightning strokes with high energy, in spite of installation of conventional protection methods. In order to reduce the number of failures of surge arresters, we should consider another protection method, such as an increase in the withstand capability of surge arresters and installation of additional overhead ground wires. However, quantitative comparison of these methods for preventing damage to surge arresters against lightning strokes with high energy has never been performed. This paper describes the effects of additional overhead ground wires for preventing damage to surge arresters. The main results are: (1) The failure rate of surge arresters on a distribution line with two overhead ground wires is about one third of that with an overhead ground wire. (2) Installation of a second overhead ground wire six to eight spans from the end of a line reduces the failure rate of a surge arrester at the end as effectively as increasing the withstand capability by a factor of two. (C) 1998 Scripta Technica.
引用
收藏
页码:12 / 20
页数:9