Predictive model for drinking water treatment technology design - the efficiency of arsenic removal by in-situ formed ferric-hydroxide

被引:3
作者
Laky, Dora [1 ]
机构
[1] BME, Dept Sanit & Environm Engn, H-1111 Budapest, Hungary
来源
PERIODICA POLYTECHNICA-CIVIL ENGINEERING | 2010年 / 54卷 / 01期
关键词
Arsenic removal; Coagulation; Drinking water; Jar-test; Linear regression analysis; Silicate; COAGULATION; ADSORPTION; SILICATE;
D O I
10.3311/pp.ci.2010-1.05
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Coagulation by ferric-salt is a widely used technique for arsenic removal. Jar tests with synthetic water were conducted in order to investigate the combined effect of the raw water characteristics on the removal efficiency of in-situ formed ferric-hydroxide. Multiple linear regression analysis was carried to establish a robust model, which is able to estimate the residual arsenic concentration provided that the raw water contained 50-60 mu g/L initial arsenic concentration. The estimation was based on the following variables: PO(4)-P concentration, final pH, SiO(2) concentration and Fe(3+) dose. The major factors influencing efficacy were the silicate concentration and applied coagulant dosage. The model was verified by data from 24 additional experiments, and the predicted and measured residual arsenic concentrations showed good agreement (R(2) = 0.87).
引用
收藏
页码:45 / 51
页数:7
相关论文
共 21 条
[1]  
CHENG RC, 1994, J AM WATER WORKS ASS, V86, P79
[2]  
Dzombak D.A., 1990, SURFACE COMPLEXATION
[3]  
EDWARDS M, 1994, J AM WATER WORKS ASS, V86, P64
[4]   Application of ZW-1000 membranes for arsenic removal from water sources [J].
Floch, J ;
Hideg, M .
DESALINATION, 2004, 162 (1-3) :75-83
[5]   Arsenic removal during conventional aluminium-based drinking-water treatment [J].
Gregor, J .
WATER RESEARCH, 2001, 35 (07) :1659-1664
[6]   Arsenic removal from drinking water by flocculation and microfiltration [J].
Han, BB ;
Runnells, T ;
Zimbron, J ;
Wickramasinghe, R .
DESALINATION, 2002, 145 (1-3) :293-298
[7]   The formation of supramolecular arrays in copper sulfimide complexes via aerial CO2 fixation;: the X-ray crystal structures of [Cu(Ph2SNH)4]2(HCO3)2(trans-O2CCHCHCO2)•4H2O, Cu(Ph2SNH)2(η2-CO3) and Cu(Ph2SNH)2(η2-CO3)•H2O [J].
Holmes, KE ;
Kelly, PF ;
Elsegood, MRJ .
CRYSTENGCOMM, 2002, 4 :174-177
[8]  
KELEMEN B, 1991, ARSENIC REMOVAL WATE
[9]  
LAKY D, 2007, P IWA UKS YOUNG WAT, P44
[10]  
LICSKO I, 1990, P 4 GOTH S OCT 1 3 1, P55