Optimal Controller Design for Transient Stability Enhancement of Grid-Following Converters Under Weak-Grid Conditions

被引:29
作者
Taul, Mads Graungaard [1 ]
Wu, Chao [1 ]
Chou, Shih-Feng [1 ]
Blaabjerg, Frede [1 ]
机构
[1] Aalborg Univ, Dept Energy Technol, DK-9220 Aalborg, Denmark
关键词
Power system stability; Automatic voltage control; Phase locked loops; Transient analysis; Stability criteria; Robustness; Thermal stability; Grid-connected converters; nonlinear analysis; reduced-order modeling; transient stability; SURROGATE MODELS; SYNCHRONIZATION; INSTABILITY; BIFURCATION; STRATEGY;
D O I
10.1109/TPEL.2021.3066205
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Modeling and design-oriented control of transient stability of grid-following converters have attained an increasing interest in recent years. Despite novel nonlinear models enabling a design-oriented enhanced transient stability controller, the focus has so far been limited to study only the synchronization dynamics of the phase-locked loop. To expand upon the knowledge of the large-signal performance and stability, this article proposes a systematic analysis procedure of a grid-following converter under weak-grid conditions and large-signal disturbances including the outer dc-link and ac-side voltage control loops. A reduced-order large-signal model is used to analyze the large-signal nonlinear behavior of the system using the area of the basin of attraction as a measure for large-signal robustness. Here, stabilizing and destabilizing trends for outer-loop controller parameters are given. Through a surrogate-model expensive black-box optimization algorithm, a computational-efficient optimal design of the outer-loop controller parameters is proposed to maximize the large-signal robustness. Finally, a recommendation and a design guideline for converter constraints and outer-loop controller parameters are given. This can be used to identify the influencing parameters for grid-following converters under large-signal disturbances, and as a tool for fast controller optimization toward large-signal robustness.
引用
收藏
页码:10251 / 10264
页数:14
相关论文
共 38 条
  • [1] Analysis of Phase-Locked Loop Low-Frequency Stability in Three-Phase Grid-Connected Power Converters Considering Impedance Interactions
    Dong, Dong
    Wen, Bo
    Boroyevich, Dushan
    Mattavelli, Paolo
    Xue, Yaosuo
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (01) : 310 - 321
  • [2] Dong D, 2013, APPL POWER ELECT CO, P439, DOI 10.1109/APEC.2013.6520247
  • [3] Synchronization and Reactive Current Support of PMSG-Based Wind Farm During Severe Grid Fault
    Geng, Hua
    Liu, Lu
    Li, Ruiqi
    [J]. IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2018, 9 (04) : 1596 - 1604
  • [4] Instability of Wind Turbine Converters During Current Injection to Low Voltage Grid Faults and PLL Frequency Based Stability Solution
    Goksu, Omer
    Teodorescu, Remus
    Bak, Claus Leth
    Iov, Florin
    Kjaer, Philip Carne
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (04) : 1683 - 1691
  • [5] Passivity-Based Controller Design of Grid-Connected VSCs for Prevention of Electrical Resonance Instability
    Harnefors, Lennart
    Yepes, Alejandro G.
    Vidal, Ana
    Doval-Gandoy, Jesus
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (02) : 702 - 710
  • [6] He X, 2018, 2018 IEEE INT C COMM, P1, DOI DOI 10.1109/VTCSPRING.2018.8417646
  • [7] Transient Stability Analysis and Enhancement of Renewable Energy Conversion System During LVRT
    He, Xiuqiang
    Geng, Hua
    Li, Ruiqi
    Pal, Bikash Chandra
    [J]. IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2020, 11 (03) : 1612 - 1623
  • [8] Heemels WPMH, 2012, IEEE DECIS CONTR P, P3270, DOI 10.1109/CDC.2012.6425820
  • [9] Large Signal Synchronizing Instability of PLL-Based VSC Connected to Weak AC Grid
    Hu, Qi
    Fu, Lijun
    Ma, Fan
    Ji, Feng
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2019, 34 (04) : 3220 - 3229
  • [10] Hu Q, 2014, INT C ELECTR MACH SY, P2618, DOI 10.1109/ICEMS.2014.7013943