A fuzzy dissolved gas analysis method for the diagnosis of multiple incipient faults in a transformer

被引:188
作者
Su, Q [1 ]
Mi, C
Lai, LL
Austin, P
机构
[1] Monash Univ, Clayton, Vic 3168, Australia
[2] Harbin Tech Univ, Harbin, Peoples R China
[3] City Univ London, London EC1V 0HB, England
[4] PowerNet Pty Ltd, Melbourne, Vic, Australia
基金
澳大利亚研究理事会;
关键词
transformer; insulation diagnosis; fuzzy logic; dissolved gas analysis;
D O I
10.1109/59.867146
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Dissolved gas analysis (DGA) of transformer oil has been one of the most useful techniques to detect the incipient faults, Various methods, such as the IEC codes, have been developed to interpret DGA results directly obtained from a chromatographer, Although these methods are widely used in the world, they sometimes fail to diagnose, especially when more than one fault exist in a transformer. This paper presents a fuzzy logic technique which can diagnose multiple faults in a transformer and quantitatively indicates the likelihood/severity of each fault. Insulation deterioration at each fault location can then be monitored closely according to its trend, which is important for a transformer in critical situation. Tests using this technique on a number of transformers have given promising results.
引用
收藏
页码:593 / 598
页数:6
相关论文
共 11 条
  • [1] BELL S, 1992, CAUCHY TRANSFORM POT
  • [2] DORNENBURG E, 1974, BROWN BOVERI REV, V61, P238
  • [3] Developing a new transformer fault diagnosis system through evolutionary fuzzy logic
    Huang, YC
    Yang, HT
    Huang, CL
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (02) : 761 - 767
  • [4] IEC, 1978, IEC PUBL, V599
  • [5] IEEE, 1991, C571041991 IEEE
  • [6] KELLY JJ, 1980, IEEE T IND APPL, V16, P777, DOI 10.1109/TIA.1980.4503871
  • [7] AN EXPERT SYSTEM FOR TRANSFORMER FAULT-DIAGNOSIS USING DISSOLVED-GAS ANALYSIS
    LIN, CE
    LING, JM
    HUANG, CL
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (01) : 231 - 238
  • [8] IEEE AND IEC CODES TO INTERPRET INCIPIENT FAULTS IN TRANSFORMERS, USING GAS IN OIL ANALYSIS
    ROGERS, RR
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1978, 13 (05): : 349 - 354
  • [9] A FUZZY INFORMATION APPROACH TO INTEGRATING DIFFERENT TRANSFORMER DIAGNOSTIC METHODS
    TOMSOVIC, K
    TAPPER, M
    INGVARSSON, T
    KALRA, PK
    SRIVASTAVA, SC
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (03) : 1638 - 1646
  • [10] WANG Z, 1998, IEEE PES WINT M FEB