Water spray for pre-cooling of inlet air for Natural Draft Dry Cooling Towers - Experimental study

被引:58
作者
Alkhedhair, Abdullah [1 ]
Guan, Zhiqiang [1 ]
Jahn, Ingo [1 ]
Gurgenci, Hal [1 ]
He, Suoying [1 ]
机构
[1] Univ Queensland, Sch Mech & Min Engn, Queensland Geothermal Energy Ctr Excellence, Brisbane, Qld 4072, Australia
关键词
Natural draft; Spray; Pre-cooling; Evaporation; Droplet; Spray efficiency; FLOW;
D O I
10.1016/j.ijthermalsci.2014.11.029
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper deals with an experimental investigation of inlet air pre-cooling with water sprays aimed to enhance the performance of Natural Draft Dry Cooling Towers during high ambient temperature periods. An open-circuit wind tunnel with a test section of 1 x 1 m(2) cross section and length of 5.2 m was employed to represent an inlet flow area section in a Natural Draft Cooling Tower. Experimental measurements of droplet evaporation and air cooling are presented. Nine high pressure, hollow cone nozzles were tested at various droplet sizes, air velocities (1, 2, 3 m/s), and injection rates under different ambient conditions. The water spray was characterized using a Phase Doppler Particle Analyser (PDPA). The effects of drop size distribution and air velocity on droplet evaporation, cooling effectiveness, and coverage area were investigated. The data shows clear trends of cooling enhancement with low air velocity or small droplet size distribution. It was found that the spray cooling efficiency, to a large extent, is dependent on spray coverage area. The experimental findings will benefit optimizing spray cooling performance in Natural Draft Dry Cooling Towers and nozzle arrangement. (C) 2014 Elsevier Masson SAS. All rights reserved.
引用
收藏
页码:70 / 78
页数:9
相关论文
共 20 条
[1]   Numerical simulation of water spray for pre-cooling of inlet air in natural draft dry cooling towers [J].
Alkhedhair, Abdullah ;
Gurgenci, Hal ;
Jahn, Ingo ;
Guan, Zhiqiang ;
He, Suoying .
APPLIED THERMAL ENGINEERING, 2013, 61 (02) :416-424
[2]  
[Anonymous], 2017, Atomization and Sprays
[3]  
[Anonymous], 2009, ASHRAE Handbook|Fundamentals
[4]  
Ashwood A., 2011, HYBRID COOLING SYSTE
[5]   PHASE DOPPLER SPRAY ANALYZER FOR SIMULTANEOUS MEASUREMENTS OF DROP SIZE AND VELOCITY DISTRIBUTIONS [J].
BACHALO, WD ;
HOUSER, MJ .
OPTICAL ENGINEERING, 1984, 23 (05) :583-590
[6]  
Boulay RB, 2005, Proceedings of the ASME Power Conference 2005, Pts A and B, P167
[7]  
Chaker M., 2002, P ASME TURB EXP A
[8]   Performance evaluation of dry-cooling systems for power plant applications [J].
Conradie, AE ;
Kroger, DG .
APPLIED THERMAL ENGINEERING, 1996, 16 (03) :219-232
[9]   Comparison of PIV and PDA droplet velocity measurement techniques on two high-pressure water mist nozzles [J].
Husted, Bjarne Paulsen ;
Petersson, Per ;
Lund, Ivar ;
Holmstedt, Goran .
FIRE SAFETY JOURNAL, 2009, 44 (08) :1030-1045
[10]  
KINCAID DC, 1989, T ASAE, V32, P457, DOI 10.13031/2013.31026