Development and Type Test of a Single-Break 126-kV/40-kA-2500-A Vacuum Circuit Breaker

被引:36
作者
Yao, Xiaofei [1 ]
Wang, Jianhua [1 ]
Geng, Yingsan [1 ]
Yan, Jing [1 ]
Liu, Zhiyuan [1 ]
Yao, Jianjun [2 ]
Liu, Ping [3 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
[2] Shaanxi Ind Technol Res Inst, Xian 710049, Peoples R China
[3] Xian High Voltage Apparat Res Inst Co Ltd, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Type test; vacuum circuit breaker (VCB); vacuum interrupter; AXIAL MAGNETIC-FIELD; ARC; INTERRUPTERS; STRENGTH; CONTACTS; POWER;
D O I
10.1109/TPWRD.2015.2456033
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The objective of this paper is to present a 126-kV/40-kA-2500-A single-break vacuum circuit breaker (VCB) and its type test results based on the IEC 62271-100: 2006 and GB1984-2003 standards. A single-break 126-kV vacuum interrupter (VI), with a pair of 2/3 coil-type contacts, is used in the 126-kV VCB. The external insulation of the VI is provided by at 0.1 MPa. A spring-type operating mechanism is used to provide a closing velocity of 1.15 m/s, which is an average velocity for 4 mm before the moving contact mates with the stationary contact. The opening velocity within 20 mm, which is 1/3 of a full contact stroke of 60 mm, is 3.5 m/s. Two kinds of test circuits are used in the type tests to verify the making and breaking capabilities of this 126-kV VCB prototype. One is a direct test circuit for test duty cycles, such as out-of-phase making and breaking test duties, that is, OP1 and OP2; capacitive current switching test of class C1, that is, CC1/LC1 and CC2/LC2. The other is a synthetic circuit, used for tests, such as the terminal fault test, the short-line fault test, the double earth fault test, and the electrical endurance test of class E2. The dielectric tests of a 230-kV/1 min power frequency voltage withstand test and a 550-kV lightning impulse voltage withstand test were used to verify the dielectric withstand performance of the VCB. Experiment results presented in this paper showed that the 126-kV/40 kA-2500 A single-break VCB passed the type tests according to IEC 62271-100 and GB1984-2003.
引用
收藏
页码:182 / 190
页数:9
相关论文
共 30 条
[1]  
[Anonymous], 2006, 62271100 IEC
[2]  
[Anonymous], 2008, 3855 JBT
[3]  
[Anonymous], 1984, 19842003 GB
[4]   High-current vacuum arc appearance in nonhomogeneous axial magnetic field [J].
Chaly, AM ;
Logatchev, AA ;
Zabello, KK ;
Shkol'nik, SM .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2003, 31 (05) :884-889
[5]   Dielectric strength of double and single-break vacuum interrupters -: Experiments with real HV demonstration bottles [J].
Giere, S ;
Kärner, HC ;
Knobloch, H .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2001, 8 (01) :43-47
[6]   History of vacuum circuit breakers and recent developments in Japan [J].
Homma, M ;
Sakaki, M ;
Kaneko, E ;
Yanabu, S .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (01) :85-92
[7]   INTERRUPTION ABILITY OF VACUUM INTERRUPTERS SUBJECTED TO AXIAL MAGNETIC-FIELDS [J].
KIMBLIN, CW ;
VOSHALL, RE .
PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1972, 119 (12) :1754-1758
[8]  
Lathan R., 1995, HIGH VOLTAGE VACUUM, P184
[9]   Development of high-voltage vacuum circuit breakers in China [J].
Liu, Zhiyuan ;
Wang, Jimei ;
Xiu, Shixin ;
Wang, Zhongyi ;
Yuan, Shun ;
Jin, Li ;
Zhou, Heming ;
Yang, Ren .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2007, 35 (04) :856-865
[10]  
Matsui Y., 2006, Proceedings of the XXIInd International Symposium on Discharges and Electrical Insulation in Vacuum, P253