Seasonal Performance Analysis Of a Residential Heat Pump Using Different Fluids With Low Environmental Impact

被引:11
作者
Botticella, Francesco [1 ]
Viscito, Luca [2 ]
机构
[1] Sannio Univ, Dept Engn, Corso Garibaldi 107, I-82100 Benevento, Italy
[2] Univ Naples Federico II, Dept Ind Engn, I-80125 Naples, Italy
来源
70TH CONFERENCE OF THE ITALIAN THERMAL MACHINES ENGINEERING ASSOCIATION, ATI2015 | 2015年 / 82卷
关键词
Heat pump; HFC replacement; Propane; R1234yf; Performance analysis; SCOP; REFRIGERATION; BUILDINGS; SYSTEMS;
D O I
10.1016/j.egypro.2015.11.832
中图分类号
O414.1 [热力学];
学科分类号
摘要
The growing of the energy consumption, in particular from buildings, both residential and commercial has induced a major interest for the analysis of the seasonal performance of heat pumps. The same considerations are effective for the well-known environmental problems related to direct and indirect emissions of carbon dioxide into the atmosphere and the incentives to support energy efficiency. In this work an air to water heat pump working with R290 and HFO1234yf has been modeled and simulated using the software package IMST-ART in order to evaluate the seasonal performance. Two different types of applications were considered: fan coils and radiant heat floor panels. Different types of building are considered. The seasonal performance in heating mode, SCOP, is calculated by coupling the performance of the heat pump in different operative conditions to a heating demand curve, in two different climate zones (average and colder). The results of the simulations show better performance of the heat pump with propane in both climates and applications, which is probably due to the state of current technology of the different components. In particular, the global performance of the compressor working with R1234yf is not yet optimized. At the same time a new design of the evaporator is desirable to reduce the pressure drops with R1234yf. (C) 2015 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:878 / 885
页数:8
相关论文
共 12 条
[1]  
[Anonymous], 2013, 148252013 EN EUR COM
[2]  
[Anonymous], 2014, Africa Energy Outlook: A Focus on Energy Prospects in Sub-Saharan Africaa Special Report in the 2014
[3]  
Corberan JM, 2008, 9 INT IEA HEAT PUMP
[4]   Influence of the source and sink temperatures on the optimal refrigerant charge of a water-to-water heat pump [J].
Corberan, Jose-M. ;
Martinez-Galvan, Israel ;
Martinez-Ballester, Santiago ;
Gonzalvez-Macia, Jose ;
Royo-Pastor, Rafael .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (04) :881-892
[5]   Simulation study of a heat pump for simultaneous heating and cooling coupled to buildings [J].
Ghoubali, Redouane ;
Byrne, Paul ;
Miriel, Jacques ;
Bazantay, Frederic .
ENERGY AND BUILDINGS, 2014, 72 :141-149
[6]  
Gonzalvez-Macia J, 2007, 2 C IB CIENC E TECN
[7]   Drop-in energy performance evaluation of R1234yf and R1234ze(E) in a vapor compression system as R134a replacements [J].
Mota-Babiloni, Adrian ;
Navarro-Esbri, Joaquin ;
Barragan, Angel ;
Moles, Francisco ;
Peris, Bernardo .
APPLIED THERMAL ENGINEERING, 2014, 71 (01) :259-265
[8]   A method for the choice of the optimal balance-point temperature of air-to-water heat pumps for heating [J].
Naldi, Claudia ;
Morini, Gian Luca ;
Zanchini, Enzo .
SUSTAINABLE CITIES AND SOCIETY, 2014, 12 :85-91
[9]   Hydrocarbons as refrigerants in small heat pump and refrigeration systems - A review [J].
Palm, Bjoern .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (04) :552-563
[10]   A review on substitution strategy of non-ecological refrigerants from vapour compression-based refrigeration, air-conditioning and heat pump systems [J].
Sarbu, Ioan .