Modelling and experimental analysis of a GAX NH3-H2O gas-driven absorption heat pump

被引:26
作者
Aprile, Marcello [1 ]
Scoccia, Rossano [1 ]
Toppi, Tommaso [1 ]
Guerra, Marco [1 ]
Motta, Mario [1 ]
机构
[1] Politecn Milan, Dept Energy, I-20156 Milan, Italy
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2016年 / 66卷
关键词
Absorption heat pump; Ammonia-water; GAX; Experimental data; Modelling; GENERATOR; CYCLE; SIMULATION;
D O I
10.1016/j.ijrefrig.2016.02.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
The experimental analysis of a gas-driven NH3-H2O heat pump whose cycle approaches the GAX concept is carried out. Full load operation is investigated by varying hot water temperatures and partial load operation is investigated by decreasing gas input down to 50% of the full load value. Numerical simulations bolster measurements accuracy and provide insight on the variation of cycle COP and Gas Utilization Efficiency (GUE), based on gross calorific value. A nearly constant GUE of about 1.5 is found for hot water temperatures lower than 50 degrees C. The GUE steadily decreases above 50 degrees C, reaching about 1.33 at 60 degrees C. The COP varies more smoothly, from 1.73 at 45 degrees C to 1.60 at 60 degrees C. The GUE and COP reduction at 50% of the nominal gas input is 6.8% and 6.4%, respectively. Simulations suggest that performances at partial loads can improve if active control of solution mass flow rate is implemented. (C) 2016 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:145 / 155
页数:11
相关论文
共 19 条
[11]  
International Organization for Standardization, 1995, 6976 ISO
[12]   Generator absorber heat exchange based absorption cycle-A review [J].
Jawahar, C. P. ;
Saravanan, R. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2010, 14 (08) :2372-2382
[13]   An environmentally friendly GAX cycle for panel heating: PGAX cycle [J].
Kang, YT ;
Kashiwagi, T .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2000, 23 (05) :378-387
[14]  
Phillips B.A., 1990, 86X24610C OAK RIDG N
[15]  
PHILLIPS BA, 1999, INT SORPT HEAT PUMP
[16]   Performance of a residential-sized GAX absorption chiller [J].
Priedeman, DK ;
Garrabrant, MA ;
Mathias, JA ;
Stout, RE ;
Christensen, RN .
JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 2001, 123 (03) :236-241
[17]  
Sharfe J., 1986, INT J REFRIG, V9, P326
[18]  
Threlkeld J.L., 1970, THERMAL ENV ENG, V2nd
[19]  
Toppi T., 2014, IEA HEAT PUMP C 2014