Experimental validation of a EnergyPlus model: Application of a multi-storey naturally ventilated double skin facade

被引:104
作者
Andelkovic, Aleksandar S. [1 ]
Mujan, Igor [1 ]
Dakic, Stojanka [2 ]
机构
[1] Univ Novi Sad, Fac Tech Sci, Trg Dositeja Obradovica 6, Novi Sad 21000, Serbia
[2] Univ Novi Sad, Fac Econ, Segedinski Put 9-11, Subotica 24000, Serbia
关键词
Multi-storey office building; Double skin facade; EnergyPlus; Validation; Statistical indicators; TEST CELL; SIMULATION; PERFORMANCE; OPERATION;
D O I
10.1016/j.enbuild.2016.02.045
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Nowadays, energy simulation in many respects assists researchers and engineers in the design phase, as well as in the buildings operational phase. Reliability of the integrated simulation model and the knowledge and experience of the user are the cornerstones of good quality simulation prediction result. This study was preceded by a detailed and long-term experimental analysis of the building with a double-skin ventilated fa ade [10]. The paper presents results of the measurement, fine-tuning process and validation of the numerical simulation model. The simulation software tool, EnergyPlus in combination with Airflow Network Algorithm algorithm was used for the cavity air temperature and velocity prediction. When the model was verified, the criterion of eligibility were defined with the recommended statistical indicators. In order to achieve the better assessment, the validation process was done trifold: for winter, transitional and summer season. Overall, the research results highlight a very good agreement and a high level of matching between measured values and simulated results, which is a confirmation of the applied energy simulation tool. (C) 2016 Elsevier B.V. All rights reserved.
引用
收藏
页码:27 / 36
页数:10
相关论文
共 24 条
[1]  
[Anonymous], ENERGY BUILD
[2]  
[Anonymous], MEAS VER GUID MEAS V
[3]  
[Anonymous], ENERGYPLUS 8 2 ENERG
[4]  
[Anonymous], ENERGYPLUS 8 2 ENG R
[5]  
[Anonymous], 027 DCE
[6]  
[Anonymous], 2002, ASHRAE GUID 14 MEAS
[7]  
[Anonymous], INT PERF MEAS VER PR
[8]   Investigation on energy performance of double skin facade in Hong Kong [J].
Chan, A. L. S. ;
Chow, T. T. ;
Fong, K. F. ;
Lin, Z. .
ENERGY AND BUILDINGS, 2009, 41 (11) :1135-1142
[9]   Operation and control strategies for multi-storey double skin facades during the heating season [J].
Choi, Wonjun ;
Joe, Jaewan ;
Kwak, Younghoon ;
Huh, Jung-Ho .
ENERGY AND BUILDINGS, 2012, 49 :454-465
[10]   Numerical modelling of ventilated facades: A review [J].
De Gracia, Alvaro ;
Castell, Albert ;
Navarro, Lidia ;
Oro, Eduard ;
Cabeza, Luisa F. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 22 :539-549