Studies of on-line monitoring of pressure in vacuum interrupters

被引:0
作者
Mao, Huiyong [1 ]
Wang, Yi [1 ]
机构
[1] Beijing Jiaotong Univ, Sch Elect Engn, Beijing 100044, Peoples R China
来源
2006 IEEE/PES POWER SYSTEMS CONFERENCE AND EXPOSITION. VOLS 1-5 | 2006年
关键词
inverted magnetron gauge; low-power consumption; on-line monitoring; pressure measurement; pulsed discharge; vacuum interrupters;
D O I
10.1109/PSCE.2006.296194
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Some methods for on-line monitoring of pressure in vacuum interrupters were reviewed. Experiments were carried out to investigate the characteristics of an inverted magnetron vacuum gauge in pulsed discharge mode, which can measure pressures ranging from 3X10-4Pa to 0.5Pa. According to the experimental results, a kind of vacuum tube with intellectualized vacuum sensor was developed to implement the on-line monitoring of pressure in vacuum interrupters. Discharge in the vacuum sensor was performed in a pulsed mode. The vacuum sensor was powered by batteries and was able to communicate the results of measurement to other devices by radio, infrared or optical fibre.
引用
收藏
页码:1851 / +
页数:3
相关论文
共 22 条
[1]  
BECK AH, 1952, VACUUM, V2, P137
[2]  
CONN GKT, 1953, VACUUM, V3, P24
[3]   PRESSURE ESTIMATION IN VACUUM CIRCUIT-BREAKERS [J].
DAMSTRA, GC ;
SMEETS, RPP ;
POULUSSEN, HBF .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1995, 2 (02) :198-201
[4]  
Damstra GC, 1998, P INT SYMP DISCH EL, V18, P443, DOI 10.1109/DEIV.1998.738629
[5]   ELECTRICAL METHODS FOR VERIFYING INTERNAL-PRESSURE OF VACUUM INTERRUPTERS AFTER LONG-TIME SERVICE [J].
FRONTZEK, FR ;
KONIG, D ;
HEINEMEYER, R .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1993, 28 (04) :635-641
[6]   OPERATION OF AN INVERTED-MAGNETRON GAUGE IN THE PRESSURE RANGE 10-3 TO 10-12 MM HG [J].
HOBSON, JP ;
REDHEAD, PA .
CANADIAN JOURNAL OF PHYSICS, 1958, 36 (03) :271-288
[7]  
JENSEN RL, 1961, J APP PHYS, V32, P2619
[8]  
KAGEYAMA K, 1974, JPN J APPL PHYS, P109
[9]   FORMATIVE PROCESSES OF COLD-CATHODE PENNING DISCHARGES AT LOW-PRESSURES [J].
KAGEYAMA, K .
JOURNAL OF APPLIED PHYSICS, 1984, 55 (03) :723-731
[10]   Starting delays in cold-cathode gauges at low pressures [J].
Kendall, BRF ;
Drubetsky, E .
JOURNAL OF VACUUM SCIENCE & TECHNOLOGY A, 1996, 14 (03) :1292-1296