Analysis and Improvement of the Multiple Controller Interaction in LCC-HVDC for Mitigating Repetitive Commutation Failure

被引:33
作者
Hong, Lerong [1 ]
Zhou, Xiaoping [1 ]
Liu, Yifeng [1 ]
Xia, Haitao [1 ]
Yin, Hanhang [1 ]
Chen, Yandong [1 ]
Zhou, Leming [1 ]
Xu, Qianming [1 ]
机构
[1] Hunan Univ, Coll Elect & Informat Engn, Changsha 410082, Peoples R China
基金
中国国家自然科学基金;
关键词
Inverters; Rectifiers; Switches; Process control; HVDC transmission; Voltage control; LCC-HVDC; commutation failure; HVDC control; controller interaction; fault recovery; STRATEGY;
D O I
10.1109/TPWRD.2020.3017802
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In a line-commutated converter based high-voltage direct-current (LCC-HVDC) system, the inverter control system usually includes constant extinction angle (CEA) controller, constant current (CC) controller, current error controller (CEC), and voltage-dependent current order limiter (VDCOL). However, the interaction influence of multiple controllers may cause repetitive commutation failure (CF). For this purpose, this paper deeply investigates the mechanism and the influencing factors of repetitive CF caused by controller interaction. It is found that the lower limit value of CEA controller can affect the control switching process and thus the probability of repetitive CF. Besides, the minimum gamma measurement (MGM) unit prevents the system from acquiring the real extinction angle in time, which results in the DC current fluctuation during the recovery process. Moreover, the probability of control-induced repetitive CF is much higher when the HVDC inverter is connected to a weak AC system or the AC fault is not serious but not cleared in time. Based on the above analyses, an improved control method is proposed for recovery performance improvement, which is mainly realized by modifying the lower and upper limits of the CEA controller during recovery. Finally, the simulation and experimental results verify the theoretical analyses and the proposed control method.
引用
收藏
页码:1982 / 1991
页数:10
相关论文
共 33 条
[1]  
Amita, 2015, J EMERG RES MANAGE T, V4, P70
[2]  
[Anonymous], 2011, P IEEE POW TECH TRON
[3]   An Evolved Capacitor-Commutated Converter Embedded With Antiparallel Thyristors Based Dual-Directional Full-Bridge Module [J].
Guo, Chunyi ;
Yang, Zhizhong ;
Jiang, Bisong ;
Zhao, Chengyong .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (02) :928-937
[4]  
[郭春义 Guo Chunyi], 2016, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V36, P4930
[5]   Power Component Fault Detection Method and Improved Current Order Limiter Control for Commutation Failure Mitigation in HVDC [J].
Guo, Chunyi ;
Liu, Yuchao ;
Zhao, Chengyong ;
Wei, Xiaoguang ;
Xu, Weihua .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (03) :1585-1593
[6]   Decreasing the commutation failure frequency in HVDC transmission systems [J].
Hansen, A ;
Havemann, K .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (03) :1022-1026
[7]  
Li C. D, 2017, P 13 IET INT C AC DC, P1
[8]  
Li C. H., 2018, AUTOMATION ELECT POW, V42, P56
[9]   Enhancement of Commutation Reliability of an HVDC Inverter by Means of an Inductive Filtering Method [J].
Li, Yong ;
Liu, Fang ;
Luo, Longfu ;
Rehtanz, Christian ;
Cao, Yijia .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2013, 28 (11) :4917-4929
[10]   Realization of Reactive Power Compensation Near the LCC-HVDC Converter Bridges by Means of an Inductive Filtering Method [J].
Li, Yong ;
Luo, Longfu ;
Rehtanz, Christian ;
Rueberg, Sven ;
Liu, Fusheng .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2012, 27 (09) :3908-3923