Performance analysis of four-partition desiccant wheel and hybrid dehumidification air-conditioning system

被引:74
作者
Jeong, Jongsoo [1 ]
Yamaguchi, Seiichi [1 ]
Saito, Kiyoshi [1 ]
Kawai, Sunao [1 ]
机构
[1] Waseda Univ, Sch Fundamental Sci & Engn, Dept Appl Mech & Aerosp Engn, Shinjuku Ku, Tokyo 1698555, Japan
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2010年 / 33卷 / 03期
关键词
Air conditioning; Desiccant system; Desiccant wheel; Geometry; Modelling; Simulation; Performance; Silica gel;
D O I
10.1016/j.ijrefrig.2009.12.001
中图分类号
O414.1 [热力学];
学科分类号
摘要
A desiccant dehumidification system with air can decrease energy consumption because it can be driven by low-grade waste heat below 80 degrees C. If this system can be driven by low-temperature heat sources whose temperature is below 50 degrees C, exhausted heat from fuel cells or air conditioners that exist everywhere can be used as heat sources. This could lead to considerable energy saving. This study provides a detailed evaluation of the performance of a four-partition desiccant wheel to make a low-temperature driving heat source possible and achieve considerable energy saving by the simulation and experiment. Further, the study investigates the in-depth performance of a hybrid air-conditioning system with a four-partition desiccant wheel by simulation. As a result, it was clear that there exists an optimum rotational speed to maximize the dehumidification performance and that the hybrid air-conditioning system improves COP by approximately 94% as compared to the conventional vapour compression-type refrigerator. (C) 2009 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:496 / 509
页数:14
相关论文
共 13 条
[1]  
[Anonymous], 2001, ASHRAE HDB FUND
[2]  
Barlow R. S., 1982, 6311330 TR SOL EN RE
[3]   Studies on solid desiccant based hybrid air-conditioning systems [J].
Dhar, PL ;
Singh, SK .
APPLIED THERMAL ENGINEERING, 2001, 21 (02) :119-134
[4]   Experimental investigation on a one-rotor two-stage rotary desiccant cooling system [J].
Ge, T. S. ;
Dai, Y. J. ;
Wang, R. Z. ;
Li, Y. .
ENERGY, 2008, 33 (12) :1807-1815
[5]  
HARRIMAN LG, 1994, HEATING PIPING A JUL, P77
[6]  
INAGAKI K, 2004, 10 INT REFR AIR CO R, V152, P1
[7]   Analysis on a hybrid desiccant air-conditioning system [J].
Jia, C. X. ;
Dai, Y. J. ;
Wu, J. Y. ;
Wang, R. Z. .
APPLIED THERMAL ENGINEERING, 2006, 26 (17-18) :2393-2400
[8]  
MECKLER M, 1994, HEATING PIPING AIR C, P75
[9]   LAMINAR-FLOW FRICTION AND FORCED-CONVECTION HEAT-TRANSFER IN DUCTS OF ARBITRARY GEOMETRY [J].
SHAH, RK .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1975, 18 (7-8) :849-862
[10]  
SHIBAO Y, 2006, P 2006 JSRAE ANN C, P257