SECOND LAW ANALYSIS OF AN ENVIRONMENTALLY FRIENDLY R290/R600/R600a MIXTURE IN A WATER-COOLED HEAT PUMP UNIT

被引:1
作者
Menlik, Tayfun [1 ]
Ozcan, Hasan [2 ]
Arcaklioglu, Erol [3 ]
机构
[1] Gazi Univ, Fac Technol, Dept Energy Syst Engn, TR-06500 Ankara, Turkey
[2] Univ Ontario, Inst Technol, Oshawa, ON, Canada
[3] Karabuk Univ, Fac Engn, Dept Mech Engn, Karabuk, Turkey
关键词
R134a; Hydrocarbon Mixture; Heat Pump; Global warming; Second law analysis; DOMESTIC REFRIGERATOR; ALTERNATIVE REFRIGERANTS; HYDROCARBON MIXTURES; REPLACE HFC-134A; SYSTEM; DRYER; R134A;
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, second law analysis of environmentally friendly R2901R600/R600a mixture at a rate of 45/46/9 % by mass fraction has been experimentally executed on a water-cooled heat pump as a substitute for HFC134a at varying air and water mass flow rates. Experimental outputs indicate that the heat pump system shows the highest exergy efficiency at 0.040 kg s-1 of water mass flow rate and 0.1 kg s-1 of air mass flow rate running with both R134a and HC mixture. Even though proposed HC mixture has lower COP and rational efficiencies, cooling exergy efficiency of HC mixture is 2-3% better than that of R134a. Higher energy consumption and lower rational efficiencies can be resolved by a hermetic compressor with higher sweep volume which is compatible with pure and mixture hydrocarbons.
引用
收藏
页码:19 / 28
页数:10
相关论文
共 23 条
[1]   Drying of mint leaves in a solar dryer and under open sun: Modelling, performance analyses [J].
Akpinar, E. Kayak .
ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (12) :2407-2418
[2]  
Aktas M, 2010, ISI BILIM TEK DERG, V30, P111
[3]  
[Anonymous], 2001, 60079 IEC
[4]  
[Anonymous], 1995, SPEC SAF ENV ASP DES, P120
[5]  
[Anonymous], 2002, NIST reference fluid thermodynamic and transport properties REFPROP
[6]  
[Anonymous], 1987, MONTREAL PROTOCOL SU
[7]  
Dalkilic AS, 2012, ISI BILIM TEK DERG, V32, P67
[8]  
Dincer I, 2007, EXERGY: ENERGY, ENVIRONMENT AND SUSTAINABLE DEVELOPMENT, P91, DOI 10.1016/B978-008044529-8.50010-0
[9]   Assessment of propane/commercial butane mixtures as possible alternatives to R134a in domestic refrigerators [J].
Fatouh, M. ;
El Kafafy, M. .
ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (15-16) :2644-2658
[10]   Experimental evaluation of a domestic refrigerator working with LPG [J].
Fatouh, M. ;
El Kafafy, M. .
APPLIED THERMAL ENGINEERING, 2006, 26 (14-15) :1593-1603