Non-Unit Ultra-High-Speed DC Line Protection Method for HVDC Grids Using First Peak Time of Voltage

被引:33
|
作者
Zhang, Chenhao [1 ]
Song, Guobing [1 ]
Dong, Xinzhou [2 ]
机构
[1] Xi An Jiao Tong Univ, Dept Elect Engn, Xian 710049, Shaanxi, Peoples R China
[2] Tsinghua Univ, Dept Elect Engn, State Key Lab Control & Simulat Power Syst & Gene, Beijing 100084, Peoples R China
关键词
Circuit faults; HVDC transmission; Impedance; Inductors; Fault detection; Sensitivity; Power transmission lines; First peak time of line-mode fault component voltage; high sensitivity; HVDC grid; ultra-high-speed dc line protection; FAULT-DETECTION; SYSTEMS;
D O I
10.1109/TPWRD.2020.3013021
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The high-speed and selective dc line protection method is required for the safe operation of HVDC grids. In this paper, the expressions of the line-mode fault component voltage at the line end as well as its first peak time (FPT) when different internal and external faults occur are derived respectively. The conclusion proves that the FPT of line-mode fault component voltage for internal faults is smaller than that for backward and forward external faults, which is independent of fault impedance and fault type as well. Then a FPT-based non-unit ultra-high-speed dc line protection method for HVDC grids is proposed. The algorithm is verified by a four terminal +/- 400 kV MMC-HVDC grid PSCAD test model as well as implemented in the developed protection device and validated by the Zhangjiakou-Beijing MMC-HVDC grid RTDS test system. The test results show that i) the FPT-based protection algorithm is independent of fault impedance and fault type, ii) the proposed method can fast and correctly identify dc line faults in the HVDC grids, even with 500 omega fault impedance, and iii) the sensitivity and fault identification time of the proposed method meet the engineering requirement of MMC-HVDC grids for dc line protection.
引用
收藏
页码:1683 / 1693
页数:11
相关论文
共 10 条
  • [1] Non-Unit Ultra-High-Speed Line Protection for Multi-Terminal Hybrid LCC/MMC HVDC System and Its Application Research
    Zhang, Chenhao
    Huang, Jinhai
    Song, Guobing
    Dong, Xinzhou
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (05) : 2825 - 2838
  • [2] Non-unit Traveling Wave Protection of HVDC Grids Using Levenberg-Marquart Optimal Approximation
    Zhang, Chenhao
    Song, Guobing
    Wang, Ting
    Wu, Lei
    Yang, Liming
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (05) : 2260 - 2271
  • [3] An Improved Non-Unit Traveling Wave Protection Method With Adaptive Threshold Value and Its Application in HVDC Grids
    Zhang, Chenhao
    Song, Guobing
    Wang, Ting
    Dong, Xinzhou
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (04) : 1800 - 1811
  • [4] Non-unit travelling wave protection method for dc transmission line using waveform correlation calculation
    Zhang, Chenhao
    Song, Guobing
    Yang, Liming
    Dong, Xinzhou
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (12) : 2263 - 2270
  • [5] Ultra-High-Speed Traveling-Wave-Based Protection Scheme for Medium-Voltage DC Microgrids
    Saleh, Khaled A.
    Hooshyar, Ali
    El-Saadany, Ehab
    IEEE TRANSACTIONS ON SMART GRID, 2019, 10 (02) : 1440 - 1451
  • [6] Principle of ultra-high-speed protection for DC transmission line based on inversion transformation of wavefront
    Zhang, Chenhao
    Song, Guobing
    Han, Wei
    Shi, Guang
    Liu, Chao
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 1382 - 1387
  • [7] Principle of Non-unit Traveling Wave Protection for VSC-HVDC Grids Based on Index of Fault Voltage Traveling Wave Propagation Term
    Zhang C.
    Song G.
    Li Y.
    Yan J.
    Dong X.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (24): : 8424 - 8436
  • [8] Ultra-High-Speed Transmission Line Differential Protection using an Error Index of Bergeron Equation
    Quispe, H. Juan Carlos
    Morales, John
    Orduna, Eduardo
    IEEE LATIN AMERICA TRANSACTIONS, 2021, 19 (07) : 1182 - 1190
  • [9] Non-unit protection scheme for flexible DC transmission lines based on fitting the rate of change of line-mode voltage reverse traveling waves
    Zhang, Qixuan
    Li, Haifeng
    Liu, Hainan
    Wang, Zhijie
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2025, 164
  • [10] A sensitive single-end DC line fault detection method for MMC-HVDC grids using reactor voltage ratio
    Yu, Senlin
    Wang, Xiaoru
    Zhang, Xiao-Ping
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 148