Concerning exergy efficiency evaluation of heat recovery exchangers for air handling units

被引:12
|
作者
Martinaitis, Vytautas [1 ]
Streckiene, Giedre [1 ]
机构
[1] Vilnius Gediminas Tech Univ, Dept Bldg Energet, Sauletekio Ave 11, LT-10223 Vilnius, Lithuania
关键词
exergy analysis; efficiency; heat recovery; heat exchanger; near-environmental temperature; Carnot factor; 2ND LAW; PERFORMANCE; SYSTEMS; ENERGY; DEFINITION;
D O I
10.1504/IJEX.2016.077432
中图分类号
O414.1 [热力学];
学科分类号
摘要
The energy chain of building energy services begins with primary energy resources and ends with building services systems (BSS). The analysis for such chain and its' elements should rely on fundamentals of thermodynamics. This paper pays attention to one of them that exergy efficiency is in the range of 0-1. In this study, exergy analysis of heat recovery exchangers for air handling units is carried out. Special attention is paid to the direction of thermal exergy flow when temperatures inducing heat transfer are close to a near-environmental temperature. On the basis of the proposed methodology, the dependency of exergy efficiency on dimensionless temperature and thermal recuperator efficiency is discussed. It is important to take the dimensionless temperature interval 0-1 into account. Here the exergy efficiency values are the lowest. Design and management measures should be used to avoid operating a heat exchanger there.
引用
收藏
页码:381 / 404
页数:24
相关论文
共 50 条
  • [21] Improving the energy efficiency of air-cooled heat exchangers
    Kuntysh, VB
    Bessonnyi, AN
    Brill, AA
    CHEMICAL AND PETROLEUM ENGINEERING, 1997, 33 (04) : 402 - 407
  • [22] Improving the energy efficiency of air-cooled heat exchangers
    V. B. Kuntysh
    A. N. Bessonnyi
    A. A. Brill'
    Chemical and Petroleum Engineering, 1997, 33 : 402 - 407
  • [23] Improving heat recovery using retrofitted heat pump in air handling unit with energy wheel
    Wallin, Jorgen
    Claesson, Joachim
    APPLIED THERMAL ENGINEERING, 2014, 62 (02) : 823 - 829
  • [24] Improving the efficiency of gas turbine-air bottoming combined cycle by heat exchangers and bypass control valves
    Khan, M. N.
    Osman, M.
    Alharbi, Abdulaziz R.
    Gorji, Mohammad Rahimi
    Alarifi, Ibrahim M.
    PHYSICA SCRIPTA, 2020, 95 (04)
  • [25] Energy and exergy analysis of a modified air handling unit assisted by phase change material, heat recovery unit, and solar energy
    Faramarzi, Saman
    Asadzadeh, Seyed Mohammad Mehdi
    Hassani, Mohammad Reza Mohammad
    Abdollahi, Seyyed Amirreza
    Zarehzadeh, Reza
    Mafi, Mostafa
    SCIENTIFIC REPORTS, 2024, 14 (01):
  • [26] Exergy efficiency of a ventilation heat recovery exchanger at a variable reference temperature
    Martinaitis, Vytautas
    Bielskus, Juozas
    Janusevicius, Karolis
    Bareika, Paulius
    MECHANIKA, 2017, 23 (01): : 70 - 77
  • [27] From Entropy Generation to Exergy Efficiency at Varying Reference Environment Temperature: Case Study of an Air Handling Unit
    Streckiene, Giedre
    Martinaitis, Vytautas
    Bielskus, Juozas
    ENTROPY, 2019, 21 (04)
  • [28] A numerical evaluation on the utilization of earth to air heat exchangers in arid regions Algeria
    Kaddour, Abdelmadjid
    Attia, Mohammed El Hadi
    Arici, Muesluem
    Benbelgacem, Khalfallah
    Driss, Zied
    JOURNAL OF THERMAL ENGINEERING, 2022, 8 (04): : 505 - 514
  • [29] Long-term energy and exergy analysis of heat pumps with different types of ground and air heat exchangers
    Habibi, Mohammad
    Hakkaki-Fard, Ali
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 100 : 414 - 433
  • [30] Experimental investigation of wraparound loop heat pipe heat exchanger used in energy efficient air handling units
    Jouhara, Hussam
    Meskimmon, Richard
    ENERGY, 2010, 35 (12) : 4592 - 4599