Concerning exergy efficiency evaluation of heat recovery exchangers for air handling units

被引:12
|
作者
Martinaitis, Vytautas [1 ]
Streckiene, Giedre [1 ]
机构
[1] Vilnius Gediminas Tech Univ, Dept Bldg Energet, Sauletekio Ave 11, LT-10223 Vilnius, Lithuania
关键词
exergy analysis; efficiency; heat recovery; heat exchanger; near-environmental temperature; Carnot factor; 2ND LAW; PERFORMANCE; SYSTEMS; ENERGY; DEFINITION;
D O I
10.1504/IJEX.2016.077432
中图分类号
O414.1 [热力学];
学科分类号
摘要
The energy chain of building energy services begins with primary energy resources and ends with building services systems (BSS). The analysis for such chain and its' elements should rely on fundamentals of thermodynamics. This paper pays attention to one of them that exergy efficiency is in the range of 0-1. In this study, exergy analysis of heat recovery exchangers for air handling units is carried out. Special attention is paid to the direction of thermal exergy flow when temperatures inducing heat transfer are close to a near-environmental temperature. On the basis of the proposed methodology, the dependency of exergy efficiency on dimensionless temperature and thermal recuperator efficiency is discussed. It is important to take the dimensionless temperature interval 0-1 into account. Here the exergy efficiency values are the lowest. Design and management measures should be used to avoid operating a heat exchanger there.
引用
收藏
页码:381 / 404
页数:24
相关论文
共 50 条
  • [1] The exergy efficiency assessment of heat recovery exchanger for air handling units, using a state property - Coenthalpy
    Martinaitis, Vytautas
    Streckiene, Giedre
    Bieksa, Darius
    Bielskus, Juozas
    APPLIED THERMAL ENGINEERING, 2016, 108 : 388 - 397
  • [2] Real heat recovery with air handling units
    Roulet, CA
    Heidt, FD
    Foradini, F
    Pibiri, MC
    ENERGY AND BUILDINGS, 2001, 33 (05) : 495 - 502
  • [3] Functional exergy efficiency of an air heat recovery exchanger under varying environmental temperature
    Martinaitis, Vytautas
    Streckiene, Giedre
    Bieksa, Darius
    Siupsinskas, Giedrius
    Bielskus, Juozas
    INTERNATIONAL JOURNAL OF EXERGY, 2018, 25 (02) : 93 - 116
  • [4] THE EFFECT OF MALFUNCTIONS IN AIR HANDLING UNITS ON ENERGY AND EXERGY EFFICIENCY
    Ceylan, Ilhan
    Yildiz, Gokhan
    Gurel, Ali Etem
    Ergun, Alper
    Tosun, Abdulkerim
    HEAT TRANSFER RESEARCH, 2020, 51 (11) : 1007 - 1028
  • [5] CASE STUDY OF ENERGY EFFICIENCY IN AIR HANDLING UNITS WITH HEAT EXCHANGERS FOR RESIDENTIAL APPLICATION IN LATVIA
    Plavenieks, Gatis
    Lesinskis, Arturs
    CIVIL ENGINEERING '13, PT I, 2013, 4 : 240 - 244
  • [6] Solutions for enhancement of energy and exergy efficiencies in air handling units
    Liu, Wanli
    Kalbasi, Rasool
    Afrand, Masoud
    JOURNAL OF CLEANER PRODUCTION, 2020, 257
  • [7] Energy and exergy study on indirect evaporative cooler used in exhaust air heat recovery
    Li, Wuyan
    Li, Yongcai
    Shi, Wenxing
    Lu, Jun
    ENERGY, 2021, 235
  • [8] TEMPERATURE EFFICIENCY OF ROTARY HEAT RECOVERY UNITS IN VENTILATION AND AIR CONDITIONING
    Parfentyeva, Natalia
    Samarin, Oleg
    Lushin, Kirill
    Paulauskaite, Sabina
    Valancius, Kestutis
    ENVIRONMENTAL ENGINEERING, VOLS 1-3, 2011, : 799 - +
  • [9] Functional exergy efficiency and exergy consumption behaviour for air-to-air heat exchangers operating at near-environmental temperatures
    Boelman, E. C.
    Sakulpipatsin, P.
    van der Kooi, H. J.
    Itard, L. C. M.
    Luscuere, P. G.
    INTERNATIONAL JOURNAL OF EXERGY, 2008, 5 (5-6) : 582 - 604
  • [10] Investigation of exergy efficiency in shell and helically coiled tube heat exchangers
    Alimoradi, Ashkan
    CASE STUDIES IN THERMAL ENGINEERING, 2017, 10 : 1 - 8