Testing of a dual-source heat pump coupled with flat-panel ground heat exchangers

被引:7
|
作者
Bottarelli, Michele [1 ]
机构
[1] Univ Ferrara, V Quartieri 8, I-44121 Ferrara, Italy
关键词
dual-source heat pump; flat-panel ground heat exchanger; experimental test; energy performance; ENERGY PERFORMANCE; AIR; IMPROVEMENT; SYSTEM;
D O I
10.1093/ijlct/ctz004
中图分类号
O414.1 [热力学];
学科分类号
摘要
The paper reports and analysis the preliminary tests of a dual-source heat pump prototype (DSHP) as experimental air-conditioning system for a room at the University of Ferrara (UNIFE), Italy. The prototype is composed of a common air-to-air heat pump, a geothermal closed loop, and a novel kit for coupling the air-source heat pump with the closed loop. The kit links the refrigerant circuit with a plate heat exchanger coupled with the closed loop, and automatizes the switching between air and ground by mean of a control unit which pilots valves according rules based on air-ground temperature and air humidity. As ground heat exchanger (GHE), the Flat-Panel patented by UNIFE is chosen due to its higher performance in comparison with similar shallow and horizontal GHEs. Moreover, its flat shape allows installations in narrow trenches, minimizing the digging and therefore the overall costs. By mean of a comprehensive monitoring system, the behaviour of the duo prototype-closed loop was monitored for a whole year in terms of temperatures, pressures, flow rate, electricity supply, and heat flux. Even if the first year was used for the optimization of the switching rules, the comparison with traditional air-source systems evidences the better behaviour of the DSHP, and therefore the overall energy saving. Having the possibility to partialize the closed loop, the performance was also evaluated in under/overloaded conditions of the Flat-Panels, to implement new control criteria matching DSHP control rules with closed loop length for a dynamic design of the overall system.
引用
收藏
页码:247 / 255
页数:9
相关论文
共 50 条
  • [1] On the sizing of a novel Flat-Panel ground heat exchanger in coupling with a dual-source heat pump
    Bottarelli, M.
    Bortoloni, M.
    Su, Y.
    RENEWABLE ENERGY, 2019, 142 : 552 - 560
  • [2] Energy performance of a dual air and ground source heat pump coupled with a Flat-Panel ground heat exchanger
    Bottarelli, Michele
    Zhang, Li
    Bortoloni, Marco
    Su, Yuehong
    BULGARIAN CHEMICAL COMMUNICATIONS, 2016, 48 : 64 - 70
  • [3] A numerical study on utilizing horizontal flat-panel ground heat exchangers in ground-coupled heat pumps
    Habibi, Mohammad
    Amadeh, Ali
    Hakkaki-Fard, Ali
    RENEWABLE ENERGY, 2020, 147 : 996 - 1010
  • [4] On the sizing of a flat-panel ground heat exchanger
    Bortoloni M.
    Bottarelli M.
    International Journal of Energy and Environmental Engineering, 2015, 6 (01) : 55 - 63
  • [5] Long term coupled simulation for ground source heat pump and underground heat exchangers
    Li, Shuhong
    Dong, Kefeng
    Wang, Jinyong
    Zhang, Xiaosong
    ENERGY AND BUILDINGS, 2015, 106 : 13 - 22
  • [6] Energy Analysis of a Dual-Source Heat Pump Coupled with Phase Change Materials
    Bottarelli, Michele
    Gonzalez Gallero, Francisco Javier
    ENERGIES, 2020, 13 (11)
  • [7] In-Situ Testing of Shallow Depth Helical Heat Exchangers for Ground Source Heat Pump Systems
    Alvarez-Revenga, Francisco J.
    Amende, Kevin L.
    Zarrella, Angelo
    2016 ASHRAE WINTER CONFERENCE PAPERS, 2016,
  • [8] Heat Transfer Characteristics of Various Kinds of Ground Heat Exchangers for Ground Source Heat Pump System
    Miyara, A.
    Kariya, K.
    Ali, Md. H.
    Selamat, S. B.
    Jalaluddin
    INTERNATIONAL CONFERENCE ON ENGINEERING, SCIENCE AND NANOTECHNOLOGY 2016 (ICESNANO 2016), 2017, 1788
  • [9] Numerical Simulations of a Ground Source Heat Pump System With Pile Heat Exchangers
    Oguma, Masahito
    Matsumoto, Takeshi
    Kakizaki, Takao
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2015, 7 (01)
  • [10] Efficiency of Vertical Geothermal Heat Exchangers in the Ground Source Heat Pump System
    Zeng, Heyi
    Diao, Nairen
    Fang, Zhaohong
    JOURNAL OF THERMAL SCIENCE, 2003, 12 (01) : 77 - 81