Experimental evaluation on thermal performance of an air-cooled absorption refrigeration cycle with NH3-LiNO3 and NH3-NaSCN refrigerant solutions

被引:58
|
作者
Cai, Dehua [1 ]
Jiang, Jingkai [1 ]
He, Guogeng [1 ]
Li, Keqiao [1 ]
Niu, Lijuan [1 ]
Xiao, Ruxi [1 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Energy & Power Engn, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
Absorption refrigeration; Air cooled; Single effect; Ammonia-sodium thiocyanate; Ammonia-lithium nitrate; Experimental results; AMMONIA/LITHIUM NITRATE; CONCENTRATED SOLUTIONS; COOLING SYSTEM; LIQUID AMMONIA; DRIVEN; TECHNOLOGIES; SOLUBILITY; CHILLERS; MIXTURE; HEAT;
D O I
10.1016/j.enconman.2016.04.089
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper experimentally analyzes thermal performance of an air-cooled type single effect absorption refrigeration cycle with ammonia-lithium nitrate and ammonia-sodium thiocyanate solutions as working pairs. Ammonia/salt system has simple construction, low evaporating temperature (<0 degrees C) and high working efficiency. Ammonia is one kind of environment-friendly refrigerants. Hence, ammonia/salt absorption refrigeration cycles are considered to be the most possible ones for practical application in small capacity refrigeration units. An experimental apparatus has been designed and built in Wuhan, China, to evaluate the cycle thermal performance of air-cooled type single effect ammonia/salts absorption refrigeration system. The experimental apparatus operates steadily under different working conditions. A set of tests have been conducted and the corresponding experimental data are measured and recorded to show the variation of the system performances with different system working parameters. For the NH3-LiNO3 system, the measured lowest evaporation temperature reaches -13.1 degrees C with corresponding average system COP of 0.15, and the average refrigerating capacity is about 670 W. For the NH3-NaSCN system, with a measured evaporation temperature of -7.5 degrees C, the corresponding average COP is 0.20, and the average refrigerating capacity was about 590 W. According to the experimental results, the actual measured COP of NH3-NaSCN system are in the range of 0.20-0.35, which are a little higher than that of NH3-LiNO3 system (actual measured COP ranging from 0.15 to 0.29). Under similar working condition, NH3-LiNO3 system can reach a lower evaporation temperature than that of NH3-NaSCN system. The experimental results of the present study demonstrate the feasibility and capability of ammonia/salt absorption refrigeration cycle for freezing purpose under air cooling conditions. Although the coefficient of performance of the experimental apparatus is below expectation while comparing with the theoretical results, optimization methods are put forward by the present paper for further research. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:32 / 43
页数:12
相关论文
共 28 条
  • [21] Experimental study on absorption characteristics of a falling film absorber with micro-scale NH3/LiNO3 liquid film
    Liang, Xiao
    He, Guogeng
    Wang, Jinyu
    Zhou, Sai
    Hao, Zian
    Cai, Dehua
    APPLIED THERMAL ENGINEERING, 2022, 200
  • [22] Modeling and performance analysis of an absorption chiller with a microchannel membrane-based absorber using LiBr-H2O, LiCl-H2O, and LiNO3-NH3
    de Vega, Mercedes
    Venegas, Maria
    Garcia-Hernando, Nestor
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2018, 42 (11) : 3544 - 3558
  • [23] Thermal performance of an absorption-refrigeration system with [emim]Cu2Cl5/NH3 as working fluid
    Chen, Wei
    Bai, Yang
    ENERGY, 2016, 112 : 332 - 341
  • [24] CO2 absorption in aqueous NH3 solutions: Novel dynamic modeling of experimental outcomes
    Atzori, Federico
    Barzagli, Francesco
    Varone, Alberto
    Cao, Giacomo
    Concas, Alessandro
    CHEMICAL ENGINEERING JOURNAL, 2023, 451
  • [25] Experimental and Mathematical Analysis of the Performance of a Small Scale Absorption Cycle (NH 3-H 2 O and LiBr-H 2 O)
    Abu Shaban, Nabeel
    Younes, Mai Bani
    Alkhalil, Shahnaz
    INTERNATIONAL JOURNAL OF HEAT AND TECHNOLOGY, 2024, 42 (02) : 427 - 433
  • [26] The influence of NH3-H2O-LiBr ternary working fluid on the performance and solution circulation in ammonia absorption refrigeration system
    Xu, Mengkai
    Li, Shuhong
    Jin, Zhenghao
    Jiang, Weixue
    Du, Kai
    APPLIED THERMAL ENGINEERING, 2023, 234
  • [27] Experimental investigation on the effect of TiO2 nanoparticles on the performance of NH3 - H2O- LiBr absorption refrigeration system acute accent Etude exp acute accent erimentale de l'effet des nanoparticules de TiO2 sur les performances d'un syste`me frigorifique a` absorption de NH3- H2O- LiBr
    Jin, Zhenghao
    Li, Shuhong
    Zhou, Runfa
    Xu, Mengkai
    Jiang, Weixue
    Du, Kai
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 131 : 826 - 833
  • [28] Performance evaluation of absorption chiller using LiBr+H2N(CH2)2OH+H2O, LiBr+HO(CH2)3OH+H2O, and LiBr+(HOCH2CH2)2NH+H2O as working fluids
    Kim, JS
    Park, Y
    Lee, H
    APPLIED THERMAL ENGINEERING, 1999, 19 (02) : 217 - 225