This paper proposes a novel distribution-level voltage control scheme that can compensate voltage sag and swell conditions in three-phase power systems. Faults occurring in power distribution systems or facilities in plants generally cause the voltage sag or swell. Sensitivity to voltage sags and swells varies within different applications. For sensitive loads, even a voltage sag of short duration can cause serious problems. Normally, a voltage interruption triggers a protection device, which causes the shutdown of the entire load. In order to mitigate power interruptions, this paper proposes a scheme for voltage sag support based on a pulse width modulated autotransformer. The proposed scheme is able to quickly recognize the voltage sag or swell condition, and it can correct the voltage by either boosting the input voltage during voltage sag events or reducing the voltage during swell events. The key advantage in this voltage control topology is that it uses only one controlled switch per phase to control the output voltage, thereby resulting in minimum cost per kVA. The paper presents the new voltage control topology, as well as the voltage detection method, the snubber design, and the commutation logic for the thyristor bypass switch. Experiments have been carried out to verify the validity of the proposed scheme.
引用
收藏
页码:626 / 635
页数:10
相关论文
共 12 条
[1]  
[Anonymous], 1995, BR105018 EPRI
[2]  
Bollen M.H.J., 2000, Series on Power Engineering
[3]  
Chan K, 1998, INT C HARMON QUAL PO, P561, DOI 10.1109/ICHQP.1998.759971
[4]   Design and implementation of a series voltage sag compensator under practical utility conditions [J].
Cheng, PT ;
Huang, CC ;
Pan, CC ;
Bhattacharya, S .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2003, 39 (03) :844-853
[5]   TRANSIENT-RESPONSE OF A PEAK VOLTAGE DETECTOR FOR SINUSOIDAL SIGNALS [J].
CHU, HY ;
JOU, HL ;
HUANG, CL .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 1992, 39 (01) :74-79
[6]  
HAQUE MH, 2001, P IEEE PORT POW TECH, V1, P1
[7]   Automatic voltage regulator with fast dynamic speed [J].
Kwon, BH ;
Youm, JH ;
Choi, JH .
IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS, 1999, 146 (02) :201-207
[8]  
Lee DM, 2004, IEEE IND ELEC, P957
[9]   VOLTAGE SAGS IN INDUSTRIAL-SYSTEMS [J].
MCGRANAGHAN, MF ;
MUELLER, DR ;
SAMOTYJ, MJ .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1993, 29 (02) :397-403
[10]  
Rostron J. R., 2004, U.S. Patent, Patent No. [6 750 563, 6750563]