A new method for protection zone selection in microprocessor-based bus relays

被引:31
作者
Qin, BL [1 ]
Guzman-Casillas, A [1 ]
Schweitzer, EO [1 ]
机构
[1] Schweitzer Engn Labs Inc, Pullman, WA 99163 USA
关键词
busbars; graph theory; microprocessor-based bus relays; protection zone selection; protective relaying;
D O I
10.1109/61.871347
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Use of graph theory simplifies representation of complex bus arrangements in power system stations, This paper prevents a new method, based upon graph theory, for selecting bus protection zones in microprocessor-based relays. We use a typical bus arrangement to illustrate the graphical representation of station arrangements, graph operations, and associated matrix operations. We also describe an implementation of the zone selection method and use two examples to demonstrate the advantages of the method. Using the status of switching devices in the station, the zone selection method provides the relay with real-time bus arrangement information. The bus relay uses this information to assign input currents to a differential protection zone and to select which breakers to trip for a bus fault or breaker failure.
引用
收藏
页码:876 / 887
页数:12
相关论文
共 15 条
  • [1] *AM NAT STAND, IEEE GUID PROT REL A
  • [2] Anderson PM, 1999, POWER SYSTEM PROTECT
  • [3] Blackburn J. L., 1998, PROTECTIVE RELAYING
  • [4] Chen W.K., 1997, GRAPH THEORY ITS ENG
  • [5] Elmore W. A., 1994, PROTECTIVE RELAYING
  • [6] Esztergalyos J., 1997, 24 ANN W PROT REL C
  • [7] HALF CYCLE BUS DIFFERENTIAL RELAY AND ITS APPLICATION
    FORFORD, T
    LINDERS, JR
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1974, PA93 (04): : 1110 - 1120
  • [8] FORFORD T, 1976, 3 ANN W PROT REL C S
  • [9] HAUG H, 1968, CIGRE PARIS JUN 10 2
  • [10] Kumar A., 1993, IEEE Computer Applications in Power, V6, P29, DOI 10.1109/67.238202