Improvement in the Operative Temperature Measurement of Radiant Cooling Panels

被引:0
|
作者
Moftakhari, Ardeshir
Novoselac, Atila
机构
来源
ASHRAE TRANSACTIONS 2020, VOL 126 | 2020年 / 126卷
关键词
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
Radiant systems have the potential for effective environmental control in the indoor space. When properly coupled with a chiller, they improve the chiller's efficiency by utilizing higher water temperature. When considering the interior surface temperatures in the room with radiant panels, they may cause highly non-uniform temperature distribution with the overall lower surface mean radiant temperatures (MRT). For this reason, both air and surface MRT are affecting 1) thermal comfort and 2) space cooling load of radiant systems and should be considered together. When considering overall thermal sensation in the systems comparison, the same room operative temperature (that is based on room air and MRT) should be used instead of the same air temperature, which results in effective lower daily cooling energy demand for radiant systems. However, implementation of operative temperature into the control system of radiant panels can be quite challenging because MRT sensors are prone to inaccurate and non-precise measurements. Typically, combined effect of air and MRT is measured by the globe thermometer, and this globe temperature is varying with the type of globe thermometer, operation condition of radiant systems, and geometry of the room. This study investigates the effect of different operation parameters, such as sensor shape, color, position, solar radiation, proximity to the air distribution systems, in the implementation of the operative temperature control for radiant systems. A set of experiments were carried out in the state-of-the-art Thermal Facade Laboratory at the University of Texas at Austin that enables simultaneous system and envelope performance comparisons. The results show rooms with radiant systems do possess lower mean radiant temperature (MRT) comparing to those with all-air systems. Also, the results indicate positioning the MRT sensor at the room center produce most accurate operative temperature measurement for full-sphere shape. In terms of sensor color, the black generally overestimates and the white underestimates the room operative temperature. Proximity to air distribution systems and exposure to solar radiation also deviate the measured temperature from the actual room operative temperature.
引用
收藏
页码:419 / 426
页数:8
相关论文
共 50 条
  • [11] EVALUATION OF THE RADIANT COOLING CEILING PANELS WITH A REVERSIBLE HEAT PUMP
    Rimar, Miroslav
    Fedak, Marcel
    Kulikov, Andrii
    Kulikova, Olha
    MM SCIENCE JOURNAL, 2021, 2021 : 5317 - 5321
  • [12] Dynamic variation in dew-point temperature of attached air layer of radiant ceiling cooling panels
    Wufeng Jin
    Jingda Ma
    Chen Bi
    Zhiqiang Wang
    Choi Bong Soo
    Pan Gao
    Building Simulation, 2020, 13 : 1281 - 1290
  • [13] Dynamic variation in dew-point temperature of attached air layer of radiant ceiling cooling panels
    Jin, Wufeng
    Ma, Jingda
    Bi, Chen
    Wang, Zhiqiang
    Soo, Choi Bong
    Gao, Pan
    BUILDING SIMULATION, 2020, 13 (06) : 1281 - 1290
  • [14] Sleeping pods with radiant cooling panels: A first assessment of thermal comfort and cooling capacity
    Ismail, Omar A.
    Kassem, Mahmoud A.
    Hassan, Muhammed A.
    ENERGY AND BUILDINGS, 2021, 250
  • [15] The Experimental Research on the Heating and Cooling Performance of Light Floor Radiant Panels
    Yu, Guoqing
    Yao, Yunpeng
    9TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING (ISHVAC) JOINT WITH THE 3RD INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT (COBEE), 2015, 121 : 1349 - 1355
  • [16] Designing a dedicated outdoor air system with ceiling radiant cooling panels
    Jeong, Jae-Weon
    Mumma, Stan
    ASHRAE JOURNAL, 2006, 48 (10) : 56 - +
  • [17] Role of flow architectures on the design of radiant cooling panels, a constructal approach
    Mosa, Mohamed
    Labat, Matthieu
    Lorente, Sylvie
    APPLIED THERMAL ENGINEERING, 2019, 150 : 1345 - 1352
  • [18] Design of thermoelectric radiant cooling-photovoltaic panels system in the building
    Abdulghafor, Israa Ali
    Mnati, Mohannad Jabbar
    ARCHIVES OF THERMODYNAMICS, 2022, 43 (04) : 85 - 108
  • [19] Numerical Prediction of Mean Radiant Temperature in Radiant Cooling Indoor Environments
    XING Daoming
    LI Nianping
    Journal of Thermal Science, 2022, 31 (02) : 359 - 369
  • [20] Designing a dedicated outdoor air system with ceiling radiant cooling panels
    Department of Architectural Engineering, Pennsylvania State University, University Park, PA, United States
    ASHRAE J, 2006, 10 (56-58+60+62+64+66):