A Sag Compensator That Eliminates the Possibility of Inrush Current While Powering Transformer-Coupled Loads

被引:11
作者
Bukhari, Syed Sabir Hussain [1 ]
Atiq, Shahid [2 ]
Kwon, Byung-il [3 ]
机构
[1] Sukkur Inst Business Adm, Dept Elect Engn, Sukkur 65200, Pakistan
[2] Islamia Univ Bahawalpur, Punjab 63100, Pakistan
[3] Hanyang Univ, Dept Elect Syst Engn, ERICA Campus, Ansan 426791, Gyeonggi Do, South Korea
基金
新加坡国家研究基金会;
关键词
Current control; inrush transient current; power quality; sag compensation; voltage sag; MITIGATION TECHNIQUE; SUPPLY SYSTEMS; MOTORS;
D O I
10.1109/JESTPE.2017.2654321
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Sags are the foremost power quality problem encountered by industrial consumers because they frequently cause the interruption of manufacturing processes, which can result in a significant economic loss. To resolve these problems, industrial consumers often install voltage sag compensators in critical industrial applications. However, these compensating topologies prove to be costly, and some take a few milliseconds to being operating when a sag occurs. The transformer, which is usually mounted in front of the critical load, is likely to be exposed to sag voltages during this time interval. As a result, when the compensator reinstates the load voltage, a serious magnitude of transient current begins to flow toward the sensitive load. This inrush current can either damage the equipment or activate the protection devices. In either case, the compensation will eventually fail. To eliminate the inrush current and to achieve seamless compensation for sensitive loads, we propose in this paper a sag compensator established on a customary current-regulated inverter. This compensator employs a current-regulating scheme using a stationary frame of reference to regulate the current for the load by connecting it to the secondary winding of the load transformer. We verify the operation of the proposed system through laboratory test results obtained under different possible sag types.
引用
收藏
页码:891 / 900
页数:10
相关论文
共 27 条
[1]  
[Anonymous], 2004, P1668 IEEE
[2]   Improved motor starting capability of three phase UPS inverters [J].
Ban, L ;
Ortmeyer, TH .
2004 11TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER, 2004, :678-683
[3]  
Bukhari S. S. H., 2014, P 7 IET INT C POW EL, P1
[4]   Line-interactive Uninterruptible Power Supply System Eliminating the Inrush Current Phenomenon [J].
Bukhari, Syed Sabir Hussain ;
Atiq, Shahid ;
Lipo, Thomas A. ;
Kwon, Byung-il .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2016, 44 (11) :1203-1214
[5]   A new single-phase sag compensator intended for transformer-coupled loads [J].
Bukhari, Syed Sabir Hussain ;
Kwon, Byung-Il .
IEICE ELECTRONICS EXPRESS, 2016, 13 (08)
[6]   A Cost-Effective, Single-Phase Line-Interactive UPS System that Eliminates Inrush Current Phenomenon for Transformer-Coupled Loads [J].
Bukhari, Syed Sabir Hussain ;
Atiq, Shahid ;
Lipo, Thomas A. ;
Kwont, Byung-il .
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2016, 11 (03) :675-682
[7]   Asymmetrical Fault Correction for the Sensitive Loads Using a Current Regulated Voltage Source Inverter [J].
Bukhari, Syed Sabir Hussain ;
Atiq, Shahid ;
Lipo, Thomas A. ;
Kwon, Byung-il .
ENERGIES, 2016, 9 (03)
[8]   Elimination of the Inrush Current Phenomenon Associated with Single-Phase Offline UPS Systems [J].
Bukhari, Syed Sabir Hussain ;
Atiq, Shahid ;
Kwon, Byung-il .
ENERGIES, 2016, 9 (02)
[9]  
Bukhari SSH, 2015, IEEE ENER CONV, P2710, DOI 10.1109/ECCE.2015.7310040
[10]  
Bukhari SSH, 2015, 2015 9TH INTERNATIONAL CONFERENCE ON POWER ELECTRONICS AND ECCE ASIA (ICPE-ECCE ASIA), P385, DOI 10.1109/ICPE.2015.7167815