A numerical study on the effects of exhaust locations on energy consumption and thermal environment in an office room served by displacement ventilation

被引:74
作者
Ahmed, Ahmed Qasim [1 ,2 ]
Gao, Shian [1 ]
Kareem, Ali Khaleel [1 ]
机构
[1] Univ Leicester, Dept Engn, Leicester LE1 7RH, Leics, England
[2] Middle Tech Univ, Engn Tech Coll, Air Conditioning & Refrigerat Dept, Baghdad, Iraq
关键词
Energy saving; Thermal comfort; Indoor air quality; Displacement ventilation; Contaminant removal; AIR-DISTRIBUTION SYSTEMS; HVAC SYSTEM; HEAT-SOURCE; INDOOR; COMFORT; DEPOSITION; TRANSPORT; PARTICLES; QUALITY; FLOW;
D O I
10.1016/j.enconman.2016.03.004
中图分类号
O414.1 [热力学];
学科分类号
摘要
In an office room, many factors affect the pattern of airflow, thermal comfort, indoor air quality and energy saving. In this study, the effects of the location of exhaust diffusers where the warm and contaminant air is extracted and their relation to room heat sources on thermal comfort and energy saving were investigated numerically for an office served by a displacement ventilation system. The indoor air quality in the breathing level and the inhaled zone were also evaluated. The contaminants were released from window and door frames in order to simulate the contaminants coming from outside. The amount of energy consumption and the indoor thermal environment for various exhaust locations were investigated numerically using the computational fluid dynamics techniques. The results showed that the thermal indoor environment, thermal comfort, quality of indoor air and energy saving were greatly improved by combining the exhaust outlets with some of the room's heat sources such as ceiling lamps and external walls. In particular, a 25.0% of energy saving was achieved by combining the exhaust diffuser with room's ceiling lamps. In addition, locating the exhaust diffuser near the heat sources also reduced the cooling coil load by 13.8%. The risk of a large difference in temperature between the head and foot levels, increased particle concentration in the occupied zone, as well as increased energy consumption was also clearly demonstrated when the exhaust and recirculated air outlet (return opening) were combined in one unit in the occupied boundary area that is located at 2 m away from the occupants. Thus, for the optimum energy saving and better indoor environment, the combination of the indoor heat sources with the exhaust outlet is necessary. (c) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:74 / 85
页数:12
相关论文
共 55 条
  • [1] Ahmed A, 2015, WORLD ACAD SCI ENG T, V9, P1078
  • [2] [Anonymous], 1994, ISO7730
  • [3] An experimental study of stratified flow in enclosures
    Awad, A. S.
    Calay, R. K.
    Badran, O. O.
    Holdo, A. E.
    [J]. APPLIED THERMAL ENGINEERING, 2008, 28 (17-18) : 2150 - 2158
  • [4] Bagheri H, 1987, ASHRAE T, V93
  • [5] HVAC system operational strategies for reduced energy consumption in buildings with intermittent occupancy: The case of mosques
    Budaiwi, I.
    Abdou, A.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2013, 73 : 37 - 50
  • [6] Chandrasekhar S., 1960, Radiative Heat Transfer
  • [7] Modeling particle distribution and deposition in indoor environments with a new drift-flux model
    Chen, FZ
    Yu, SCM
    Lai, ACK
    [J]. ATMOSPHERIC ENVIRONMENT, 2006, 40 (02) : 357 - 367
  • [8] Investigation on the thermal comfort and energy efficiency of stratified air distribution systems
    Cheng, Yuanda
    Niu, Jianlei
    Du, Zhenyu
    Lei, Yonggang
    [J]. ENERGY FOR SUSTAINABLE DEVELOPMENT, 2015, 28 : 1 - 9
  • [9] Experimental and numerical investigations on stratified air distribution systems with special configuration: Thermal comfort and energy saving
    Cheng, Yuanda
    Niu, Jianlei
    Liu, Xiaoping
    Gao, Naiping
    [J]. ENERGY AND BUILDINGS, 2013, 64 : 154 - 161
  • [10] Enthalpy estimation for thermal comfort and energy saving in air conditioning system
    Chu, Chi-Min
    Jong, Tai-Lang
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (06) : 1620 - 1628