Development of 550kV 63.kA one-break gas circuit breaker

被引:0
作者
Ochiai, I [1 ]
Kohyama, H [1 ]
Ito, H [1 ]
Hidaka, M [1 ]
Sugiyama, T [1 ]
Yamamoto, H [1 ]
Matuszak, D [1 ]
机构
[1] Mitsubishi Electr Corp, Amagasaki, Hyogo, Japan
来源
IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXHIBITION 2002: ASIA PACIFIC, VOLS 1-3, CONFERENCE PROCEEDINGS: NEW WAVE OF T&D TECHNOLOGY FROM ASIA PACIFIC | 2002年
关键词
gas circuit breaker; one-break; mechanical and electrical reliability; controlled switching; minimum maintenance;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The 550kV one-break gas circuit breaker (GCB) has been developed. to meet advanced mechanical and electrical reliability requirements for GCBs. An improvement of the interruption capability reduces the number of break points in the GCB, and also realizes an elimination of the grading capacitor. An application of a synchronous switching scheme eliminates the closing resistor. Introduction of these innovative technologies into the 550kV GCB realizes a reduction in the number of parts and minimizes the maintenance effort. The reduction of the break points and the reduction of the size of the SF6 gas enclosure contribute directly to decreased gas usage.
引用
收藏
页码:93 / 98
页数:6
相关论文
共 4 条
[1]  
ITO, 1997, 12 INT C GAS DISCH T, P102
[2]  
SUGIYAMA, P 1993 NAT C IEEE JA, P1455
[3]  
WADA, DEV 145KV SYNCHRONOU
[4]  
YOSHIZUMI, 1989, IEEE