Insulation Properties of Highly Pressurized Dry Air-effects of Anodic Oxide Coating and Surface Roughness of Electrodes on Breakdown Voltage

被引:6
作者
Inoue, Naoaki [1 ]
Sato, Shinji [1 ]
Yoshida, Tadahiro [2 ]
Oida, Yuki [3 ]
Kumada, Akiko [3 ]
Hidaka, Kunihiko [3 ]
机构
[1] Mitsubishi Electr Corp, Adv Tecnol R&D Ctr, Amagasaki, Hyogo 6618661, Japan
[2] Mitsubishi Electr Corp, Power Distribut Syst Ctr, Marugame 7638516, Japan
[3] Univ Tokyo, Dept Elect Engn & Informat Syst, Bunkyo Ku, Tokyo 1138656, Japan
关键词
Dry air; anodic oxide coating; surface roughness;
D O I
10.1109/TDEI.2014.003836
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Dry air has been introduced to gas-insulated switchgears as an environmentally-friendly insulation medium for SF6 gas. Since its insulation strength is about one-third of SF6 gas, to grasp the insulation properties of highly pressurized dry air is necessary to apply dry air insulation to further high voltage equipments. In this paper, to consider smaller products and higher voltage ratings, insulation properties in highly pressurized dry air was investigated. Especially, pressure dependence, surface roughness dependence and the effect of surface processes were investigated.
引用
收藏
页码:2081 / 2087
页数:7
相关论文
共 8 条
  • [1] [Anonymous], 1998, DISCHARGE HANDBOOK, P274
  • [2] [Anonymous], 1987, JEC 213
  • [3] Berz S., 2010, IEEJ ANNUAL MEETING, P6
  • [4] Investigating R& D Committee on the trend of medium-voltage switchgears technology with consideration of environmental resistance performance, 2010, TECH REP 1181
  • [5] Okubo H., 2003, IEEJ Trans. Power Energy, V123, P129
  • [6] Development of SF6-free 72.5 kV GIS
    Rokunohe, Toshiaki
    Yagihashi, Yoshitaka
    Aoyagi, Kenji
    Oolmori, Takashi
    Endo, Fumihiro
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (03) : 1869 - 1876
  • [7] Shinkai H., 2005, H02 ELECT POW ENG R
  • [8] Yoshida T., 2010, IEEJ Trans. Power Energy, V130, P621