Unit-connected generator with ground-fault neutralizer in generator neutral during ground-fault process

被引:0
|
作者
Fulczyk, M [1 ]
机构
[1] ABB Corp Res, PL-31038 Krakow, Poland
来源
IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXHIBITION 2002: ASIA PACIFIC, VOLS 1-3, CONFERENCE PROCEEDINGS: NEW WAVE OF T&D TECHNOLOGY FROM ASIA PACIFIC | 2002年
关键词
generators; grounding; protection; windings;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The 1(st) harmonic of the voltage zero-sequence component in the generator neutral during generator normal operation, during faults in the generator stator windings and in the power system and 3rd harmonic of the voltage zero-sequence component in generator neutral during normal operation and during ground-faults in stator winding are analysed. The influence of element grounding generator neutral on these all voltages for different parameters of the generator and transformer, the additional capacitance to ground of the generator breakers was determined. This influence was analyzed for generators with the ground-fault neutralizer (GFN) grounding generator neutral. The different resistances of the breakdown channel during ground-faults along the whole length of generator stator winding were considered in analysis. It has been found that for applied method of grounding the generator neutral, the level of neutralidsation of the ground-fault current as wll as the parameters of generator and transformer, the additional capacitance to ground of the generator breakers, level of fault resistance and ground-fault location have a substantial influence on these voltages. The voltage zero-sequence components in generator neutral and distribution of 3rd harmonic voltages in generator stator winding during normal generator operation and during ground-faults are determined mainly by these all parameters.
引用
收藏
页码:2362 / 2367
页数:6
相关论文
共 50 条