Experimental Investigation of Single-Phase Microjet Array Heat Transfer

被引:51
作者
Browne, Eric A. [1 ]
Michna, Gregory J. [1 ]
Jensen, Michael K. [1 ]
Peles, Yoav [1 ]
机构
[1] Rensselaer Polytech Inst, Dept Mech Aerosp & Nucl Engn, Troy, NY 12180 USA
来源
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME | 2010年 / 132卷 / 04期
关键词
heat transfer; jets; Mach number; microfluidics; REYNOLDS-NUMBER; MACH NUMBER; JETS; GAS;
D O I
10.1115/1.4000888
中图分类号
O414.1 [热力学];
学科分类号
摘要
The heat transfer performance of two microjet arrays was investigated using degassed deionized water and air. The inline jet arrays had diameters of 54 mu m and 112 mu m, a spacing of 250 mu m, a standoff of 200 mu m (S/d=2.2 and 4.6, H/d=1.8 and 3.7), and jet-to-heater area ratios from 0.036 to 0.16. Average heat transfer coefficients with deionized water were obtained for 150 < Re-d < 3300 and ranged from 80,000 W/m(2) K to 414,000 W/m(2) K. A heat flux of 1110 W/cm(2) was attained with 23 degrees C inlet water and an average surface temperature of 50 degrees C. The Reynolds number range for the same arrays with air was 300 < Re-d < 4900 with average heat transfer coefficients of 2500 W/m(2) K to 15,000 W/m(2) K. The effect of the Mach number on the area-averaged Nusselt number was found to be negligible. The data were compared with available correlations for submerged jet array heat transfer.
引用
收藏
页码:1 / 9
页数:9
相关论文
共 20 条
[1]   Optimized heat transfer for high power electronic cooling using arrays of microjets [J].
Fabbri, M ;
Dhir, VK .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2005, 127 (07) :760-769
[2]   STREAMWISE FLOW AND HEAT-TRANSFER DISTRIBUTIONS FOR JET ARRAY IMPINGEMENT WITH CROSS-FLOW [J].
FLORSCHUETZ, LW ;
TRUMAN, CR ;
METZGER, DE .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1981, 103 (02) :337-342
[3]   Local heat transfer distributions in confined multiple air jet impingement [J].
Garimella, SV ;
Schroeder, VP .
JOURNAL OF ELECTRONIC PACKAGING, 2001, 123 (03) :165-172
[4]   Heat transfer correlation for hexagonal and in-line arrays of impinging jets [J].
Geers, L. F. G. ;
Tummers, M. J. ;
Bueninck, T. J. ;
Hanjalic, K. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2008, 51 (21-22) :5389-5399
[5]   Effects of Mach number and Reynolds number on jet array impingement heat transfer [J].
Goodro, Matt ;
Park, Jongmyung ;
Ligrani, Phil ;
Fox, Mike ;
Moon, Hee-Koo .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2007, 50 (1-2) :367-380
[6]  
KERCHER DM, 1970, ASME J ENG POWER, V92, P73, DOI DOI 10.1115/1.3445306
[7]  
Kline S.J., 1952, ASME Mechanical Engineering, V75, P3, DOI DOI 10.1016/J.CHAOS.2005.11.046
[8]   Experimental investigation of an air microjet array impingement cooling device [J].
Leland, JE ;
Ponnappan, R ;
Klasing, KS .
JOURNAL OF THERMOPHYSICS AND HEAT TRANSFER, 2002, 16 (02) :187-192
[9]  
Ma C.F., 1995, Advances in Heat Transfer, V26, P105, DOI DOI 10.1016/S0065-2717(08)70296-X
[10]  
Martin H., 1977, ADV HEAT TRANSFER, V13, P1