Pillow plate heat exchanger weld shape optimization using approximation and parallel parameterized CFD and non-uniform rational B-splines

被引:16
作者
Eldeeb, Radia [1 ]
Aute, Vikrant [1 ]
Radermacher, Reinhard [1 ]
机构
[1] Univ Maryland, Ctr Environm Energy Engn, Dept Mech Engn, 3155 Glenn L Martin Hall Bldg, College Pk, MD 20742 USA
关键词
Plate heat exchangers; Optimization; Computational fluid dynamics; Air conditioning and refrigeration; Pillow plates; Chevron plates; Non-uniform rational B-splines; PRESSURE-DROP; CONDENSATION; DESIGN; EVAPORATION;
D O I
10.1016/j.ijrefrig.2019.10.024
中图分类号
O414.1 [热力学];
学科分类号
摘要
Plate heat exchangers (PHXs) are compact with small approach temperature, and desirable thermal-hydraulic characteristics. It is greatly desirable to create novel PHX designs that utilize less material and less volume while attaining similar heat transfer performance and thus contribute significantly to energy conservation while lowering the environmental impact as well. Pillow Plate Heat Exchanger (PPHX) is a type of PHX with a complex wavy structure with desirable thermal-hydraulic characteristics, but yet an economical manufacturing process especially when compared to corrugated Chevron PHX (CPHX) which requires a special die for each design. PPHX has great design flexibility allowing novel designs to be created in a simpler and less costly process which provides them with a good potential to outperform other types of PHXs. PPHXs are more commonly used in chemical and process industry with limited research in Heating, Ventilating, Air Conditioning, and Refrigeration (HVAC&R) applications. In this study, the optimization of PPHXs in order to maximize their thermal-hydraulic performance, including weld shape optimization using novel weld shapes created using Non-Uniform Rational B-Splines (NURBS), is studied. Sensitivity analysis is conducted on the optimal designs to provide insights into factors affecting their performance. The potential enhancement is up to 36% improvement in heat transfer coefficient and 67% reduction in pressure drop as compared to a selected PPHX baseline design with circular spot welds. The optimal designs are compared to optimal CPHX designs from literature showing a potential improvement of 38% for heat transfer coefficient, and a reduction of 72% in pressure drop. (C) 2019 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:121 / 131
页数:11
相关论文
共 22 条
  • [1] Approximation-Assisted Optimization for Novel Compact Heat Exchanger Designs
    Abdelaziz, Omar
    Aute, Vikrant
    Azarm, Shapour
    Radermacher, Reinhard
    [J]. HVAC&R RESEARCH, 2010, 16 (05): : 707 - 728
  • [2] ANSYS Inc, 2016, ANSYS 17 0
  • [3] ASME, 2009, Standard for Verification and Validation in Computational Fluid Dynamics and fleat Transfer: An American National Standard
  • [4] Plate heat exchanger literature survey and new heat transfer and pressure drop correlations for refrigerant evaporators
    Ayub, ZH
    [J]. HEAT TRANSFER ENGINEERING, 2003, 24 (05) : 3 - 16
  • [5] Cressie N., 1993, STAT SPATIAL DATA, DOI DOI 10.1002/9781119115151
  • [6] Deb K., 2011, KanGAL report No. 2011003
  • [7] Eldeeb R, 2016, 16 INT REFR AIR COND
  • [8] A survey of correlations for heat transfer and pressure drop for evaporation and condensation in plate heat exchangers
    Eldeeb, Radia
    Aute, Vikrant
    Radermacher, Reinhard
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 65 : 12 - 26
  • [9] Hamad H., 2006, P 2006 IEEE WINT SIM
  • [10] Incropera F.P., 2011, Fundamental of heat and mass Transfer