Characterization of a building's operation using automation data: A review and case study

被引:45
作者
Gunay, Burak [1 ,2 ]
Shen, Weiming [1 ]
Yang, Chunsheng [3 ]
机构
[1] Natl Res Council Canada, Construct Portfolio, Ottawa, ON, Canada
[2] Carleton Univ, Civil & Environm Engn, Ottawa, ON, Canada
[3] Natl Res Council Canada, Informat & Commun Portfolio, Ottawa, ON, Canada
关键词
Automated on-going commissioning; Fault detection and diagnostics; Inverse modelling; Greybox modelling; Commercial buildings; AIR-HANDLING UNITS; SENSOR FAULT-DETECTION; DIAGNOSIS STRATEGY; MULTIPLE FAULTS; NEURAL-NETWORKS; VAV TERMINALS; FLOW-RATE; PART II; MODEL; PERFORMANCE;
D O I
10.1016/j.buildenv.2017.03.035
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper presents a critical review of the automated on-going commissioning (AOGC) methods for air handling units (AHU) and variable air volume terminal (VAV) units in commercial buildings. The common faults studied in the literature were identified. The diagnostic approaches taken and the characteristics of the fault-symptom datasets utilized were categorized. It was found that the diagnostics methods were vastly fragmented, and most of them employed pure-statistical approaches. Only a few studies attempted to assimilate the automation data within the underlying physical processes. In addition, a large fraction of the reviewed literature has been devoted to physical faults in AHUs. Only a few studies were conducted to diagnose faults-related with controls programming and faults at the zone level. Upon the literature survey findings, an inverse greybox modelling-based AOGC approach was put forward. Its strengths and weaknesses were demonstrated through a case study conducted using the archived building automation system (BAS) data of an office building in Ottawa, Canada. The results of this case study indicate that inverse greybox modelling-based AOGC is a promising method to diagnose both physical and controls programming related faults at AHUs and VAVs. Crown Copyright (C) 2017 Published by Elsevier Ltd. All rights reserved.
引用
收藏
页码:196 / 210
页数:15
相关论文
共 113 条
[1]   Visualization of energy and water consumption and GHG emissions: A case study of a Canadian University Campus [J].
Abdelalim, Aly ;
O'Brien, William ;
Shi, Zixiao .
ENERGY AND BUILDINGS, 2015, 109 :334-352
[2]   Fuzzy Neural Network-Based Health Monitoring for HVAC System Variable-Air-Volume Unit [J].
Allen, William Hand ;
Rubaai, Ahmed ;
Chawla, Ramesh .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2016, 52 (03) :2513-2524
[3]  
Anis W., 2013, ASHRAE T, V119
[4]  
[Anonymous], REPORTTECHNICAL SYNT
[5]  
[Anonymous], NAT C BUILD COMM KAN
[6]  
[Anonymous], SCI TECH BUILT ENV
[7]  
[Anonymous], BUILD OPT FAULT DIAG
[8]  
[Anonymous], COMM TOOLS IMPR EN P
[9]  
[Anonymous], GETTING ZONE INTERNE
[10]  
[Anonymous], THESIS