A Pinch-Based Approach for the Synthesis of Chilled Water Network

被引:4
作者
Foo, Dominic C. Y. [1 ]
Ng, Denny K. S. [1 ]
Chew, Irene M. L. [2 ]
Lee, Jul-Yuan [3 ]
机构
[1] Univ Nottingham Malaysia, Ctr Excellence Green Technol, Broga Rd, Semenyih 43500, Selangor, Malaysia
[2] Monash Univ Sunway Campus, Sch Engn, Bandar Sunway 46150, Selangor, Malaysia
[3] Univ Witwatersrand, Sch Chem & Met Engn, Johannesburg, South Africa
来源
PRES 2014, 17TH CONFERENCE ON PROCESS INTEGRATION, MODELLING AND OPTIMISATION FOR ENERGY SAVING AND POLLUTION REDUCTION, PTS 1-3 | 2014年 / 39卷
关键词
OPTIMIZATION; SYSTEM; DESIGN;
D O I
10.3303/CET1439177
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This paper aims to address energy efficiency issue in the chilled water network (CHWN) system. Chilled water is a typical cooling agent used for heating, ventilating and air conditioning (HVAC) in various industrial, commercial and institutional facilities. In the conventional setup of CHWNs, chilled water is distributed throughout the buildings via piping connection to various HVAC heat exchangers in order to provide required air conditioning and equipment cooling. In this work, we attempt to address the problem from Process Integration perspective. The underlying principle of CHWN synthesis is to design the network in such a way that the chilled water is sent to the heat exchangers in a series fashion, rather than the conventional parallel arrangements. This enables the CHWN to be supplied with a lower flowrate of cooling water, which leads to less pumping work, and enables the chilled water return temperature to be maximized, thus increasing the chillers efficiency. A chilled water composite curve (CHWCC) is presented to determine the minimum chilled water flowrate needed for a CHWN. A network design algorithm is then used to design the CHWN to achieve the minimum chilled water flowrate. A hypothetical example is used to illustrate the newly proposed algorithm.
引用
收藏
页码:1057 / +
页数:2
相关论文
共 10 条
[1]  
Bell ArthurA., 2008, HVAC EQUATIONS DATA, V2nd
[2]   A novel energy conservation method - optimal chiller loading [J].
Chang, YC .
ELECTRIC POWER SYSTEMS RESEARCH, 2004, 69 (2-3) :221-226
[3]  
El-Halwagi M., 1997, Pollution Prevention Through Process Integration: Systematic Design Tools
[4]   HVAC system optimization for energy management by evolutionary programming [J].
Fong, KF ;
Hanby, VI ;
Chow, TT .
ENERGY AND BUILDINGS, 2006, 38 (03) :220-231
[5]   Power consumption of semiconductor fabs in Taiwan [J].
Hu, SC ;
Chuah, YK .
ENERGY, 2003, 28 (08) :895-907
[6]   Cooling water system design [J].
Kim, JK ;
Smith, R .
CHEMICAL ENGINEERING SCIENCE, 2001, 56 (12) :3641-3658
[7]   Synthesis and design of chilled water networks using mathematical optimization [J].
Lee, Jui-Yuan ;
Chen, Cheng-Liang ;
Wen, Tong-Lin ;
Ng, Denny Kok Sum ;
Foo, Dominic Chwan Yee ;
Wang, Tzu-Chi .
APPLIED THERMAL ENGINEERING, 2013, 58 (1-2) :638-649
[8]   A simulation-optimization approach for energy efficiency of chilled water system [J].
Lee, Kuei-Peng ;
Cheng, Te-Ang .
ENERGY AND BUILDINGS, 2012, 54 :290-296
[9]   Targeting and design of CWNs (cooling water networks) [J].
Shenoy, Akshay U. ;
Shenoy, Uday V. .
ENERGY, 2013, 55 :1033-1043
[10]  
Wulfinghoff D.R., 1999, ENERGY EFFICIENCY MA