Experimental Study of Fast Transient Currents in Gas Insulated Substation

被引:1
|
作者
Visakan, S. [1 ]
Rao, Mandava Mohana [2 ,3 ]
Kumar, Mritunjay [4 ]
Sunitha, K. [1 ]
机构
[1] Natl Inst Technol, Elect Engn, NITC Campus, Calicut 673601, Kerala, India
[2] BHEL R&D, GSG, Hyderabad, India
[3] BHEL R&D, Hyderabad 500093, Andhra Pradesh, India
[4] Bharat Heavy Elect Ltd Res & Dev, HVE, Hyderabad, Telangana, India
来源
INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS | 2019年 / 20卷 / 06期
关键词
gas insulated substation (GIS); fast transient currents (FTCs); fast fourier transform (FFT); ELECTROMAGNETIC-INTERFERENCE; GIS; TRANSFORMERS; OVERVOLTAGE; FIELDS;
D O I
10.1515/ijeeps-2018-0099
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The increasing demand in transmitting electrical energy at very high voltages with low transmission losses and improved efficiency has led to the development of compact metal enclosed gas insulated substation. There are various advantages of gas insulated substations over conventional substations yet there are a few problems associated with the switching operation in gas insulated substation. The fast transient voltages arising due to the switching operation of disconnectors or circuit breakers may impair the service reliability. The fast transient currents are associated with these fast transient voltages. The main aim of this paper is to characterize the fast transient currents generated due to the switching operations in a gas insulated substation. The dominant frequency content has been identified for different rise times of the fast transient currents and the percentage attenuation in amplitude is determined at different distances from the source. The variation in the peak value of current with distance from the source is also analysed. The experimental work is carried out on 145 kV gas insulated substation models of different configurations and comparison of the results for different case studies are reported.
引用
收藏
页数:13
相关论文
共 50 条
  • [1] Study of Very Fast Transient Overvoltages and Mitigation Techniques of a Gas Insulated Substation
    Pathak, Nikhil
    Bhatti, T. S.
    Ibraheem
    2015 INTERNATIONAL CONFERENCED ON CIRCUITS, POWER AND COMPUTING TECHNOLOGIES (ICCPCT-2015), 2015,
  • [2] ESTIMATION OF FAST TRANSIENT OVERVOLTAGE IN GAS-INSULATED SUBSTATION
    YANABU, S
    MURASE, H
    AOYAGI, H
    OKUBO, H
    KAWAGUCHI, Y
    IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (04) : 1875 - 1882
  • [3] Experimental study of effect of Disconnector speed on Very Fast transient Over Voltages in a 420kV Gas Insulated Substation
    Rao, J. V. G. Rama
    Ramakrishna, A.
    JOURNAL OF ELECTRICAL SYSTEMS, 2020, 16 (02) : 142 - 151
  • [4] Modeling of potential transformers in gas insulated substation for the very fast transient simulation
    Zhang, ZY
    Liang, GS
    Cui, XA
    2003 IEEE International Symposium on Electromagnetic Compatibility (EMC), Vols 1 and 2, Symposium Record, 2003, : 308 - 311
  • [5] Very fast transient overvoltage calculation and evaluation for 500-kV gas insulated substation power substation with double circuit and long gas insulated substation busbar
    Fu, Runyu
    Wang, Jianguo
    Wang, Jianping
    Zhou, Mi
    Li, Cai
    Zhao, Yating
    Fan, Yadong
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (01) : 252 - 262
  • [6] Study of gas insulated substation and its comparison with air insulated substation
    Nagarsheth, Raj
    Singh, Sushant
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 55 : 481 - 485
  • [7] Computation of Very Fast Transient Overvoltages (VFTO) in a 1000 kV Gas Insulated Substation
    Haseeb, M. A.
    Thomas, M. Joy
    2017 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2017,
  • [8] Mitigation/ Suppression Techniques of Very Fast Transient over Voltages of a Gas Insulated Substation
    Pathak, Nikhil
    Bhatti, T. S.
    Verma, Ashu
    PROCEEDINGS OF THE FIRST IEEE INTERNATIONAL CONFERENCE ON POWER ELECTRONICS, INTELLIGENT CONTROL AND ENERGY SYSTEMS (ICPEICES 2016), 2016,
  • [9] Differentiating/integrating system for the measurement of very fast transient overvoltage in gas-insulated substation
    Guangdong Power Test and Research, Inst, Guangzhou, China
    Zhongguo Dianji Gongcheng Xuebao, 5 (59-61, 29):
  • [10] Modeling of 275 kV Gas Insulated Substation and Analysis and Mitigation of Very Fast Transient Overvoltages
    Shanavas, T. N.
    Krishna, Bharath K.
    Sunny, Anglight
    Anju, P. M.
    Rajeev, Aman
    2021 INTERNATIONAL CONFERENCE ON COMPUTATIONAL PERFORMANCE EVALUATION (COMPE-2021), 2021, : 810 - 814