Phase-angle balance control for harmonic filtering of a three-phase shunt active filter system

被引:10
作者
Chattopadhyay, S [1 ]
Ramanarayanan, V [1 ]
机构
[1] Indian Inst Sci, Dept Elect Engn, Power Elect Grp, Bangalore 560012, Karnataka, India
关键词
digital-signal-processor (DSP) TMS320F240-based implementation; harmonic filter; phase-angle balance (PAB) control; shunt active filter (SAF); voltage-sensorless operation;
D O I
10.1109/TIA.2003.808941
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper proposes a new strategy for harmonic filtering of a three-phase shunt active filter system. The shunt harmonic filter's control objective is defined as: balance the phase angle of the input current with the phase angle of the line frequency component of the load current. This objective is achieved in digital implementation without sensing the input voltages. The controller uses a phase-shifting method on the sensed input current and then applies the resistor-emulator-type input-current-shaping strategy on the phase-shifted current. In implementation, Texas Instrument's digital-signal,processor-based unit TMS320F240 EVM is used as the digital. hardware platform. The control algorithm is computationally simple yet the harmonic filtering performance is high. The analysis, simulation, and experimental results of a three-phase shunt active filter prototype on a 25-A nonlinear load are presented.
引用
收藏
页码:565 / 574
页数:10
相关论文
共 8 条
[1]  
AGIRMAN I, 2001, C REC IEEE IAS ANN M, V4, P2175
[2]   INSTANTANEOUS REACTIVE POWER COMPENSATORS COMPRISING SWITCHING DEVICES WITHOUT ENERGY-STORAGE COMPONENTS [J].
AKAGI, H ;
KANAZAWA, Y ;
NABAE, A .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1984, 20 (03) :625-630
[3]  
BHATTACHARYA S, 1991, P EPE C FLOR IT, P30
[4]  
Chattopadhyay S, 2001, APPL POWER ELECT CO, P592, DOI 10.1109/APEC.2001.911707
[5]   Virtual-flux-based direct power control of three-phase PWM rectifiers [J].
Malinowski, M ;
Kazmierkowski, MP ;
Hansen, S ;
Blaabjerg, F ;
Marques, GD .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2001, 37 (04) :1019-1027
[6]   Unified constant-frequency integration control of active power filters - Steady-state and dynamics [J].
Smedley, KM ;
Zhou, LW ;
Qiao, CM .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2001, 16 (03) :428-436
[7]   An instantaneous active and reactive current component method for active filters [J].
Soares, V ;
Verdelho, P ;
Marques, GD .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2000, 15 (04) :660-669
[8]  
1997, TMS320C24X DSP CONTR, V2