Study on Aging Assessment Model of Transformer Cellulose Insulation Paper Based on Methanol in Oil

被引:15
|
作者
Chen, Qingguo [1 ]
Li, Chunpeng [1 ]
Cheng, Song [1 ]
Sun, Wei [1 ,2 ]
Chi, Minghe [1 ]
Zhang, He [1 ]
机构
[1] Harbin Univ Sci & Technol, Sch Elect & Elect Engn, Key Lab Engn Dielect & Its Applicat, Minist Educ, Harbin 150080, Peoples R China
[2] State Grid Heilongjiang Elect Power Co Ltd, Elect Power Res Inst, Harbin 150030, Peoples R China
基金
中国国家自然科学基金;
关键词
Methanol; Aging; Oils; Moisture; Temperature; Power transformer insulation; Oil insulation; Aging assessment model; degree of polymerization (DP); insulation paper; methanol; moisture; temperature; CHAIN-END GROUPS; PART; FURANIC COMPOUNDS; DEGRADATION; KINETICS; DEPOLYMERIZATION; EQUATIONS; ETHANOL; MARKERS; DP;
D O I
10.1109/TDEI.2022.3157900
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Methanol is considered to be a new chemical marker to estimate the aging state of transformer cellulose insulation paper. The key to improve the assessment accuracy is to establish the precise relationship between the concentration of methanol in oil and degree of polymerization (DP) of insulation paper. The previous research in this area has shortcomings and needs to be further improved. In this article, first, an aging assessment basic model (temperature 20 degrees C, moisture content of insulation paper 0.637%) is established based on the theoretical derivation of cellulose degradation kinetics, and is calculated by 130 degrees C thermal aging experiment. Furthermore, the effects of different temperatures (20 degrees C-90 degrees C) and moisture contents of insulation paper (0.6%-3.4%) on methanol in oil are studied by diffusion experiment. Based on the above effects, the temperature and moisture correction factors are established by mathematical reduction. What is more, a modified model is proposed by integrating the basic model and the correction factors. Eventually, the verification experiment is randomly prepared to test the accuracy of modified model and the result shows that the relative error of DP is within 7%. The physical meaning and accuracy of aging assessment are improved by model derivation and modification of influencing factors.
引用
收藏
页码:591 / 598
页数:8
相关论文
共 50 条
  • [31] Investigation on the equilibrium distribution of methanol in transformer oil-immersed cellulosic insulation
    Zheng, Hanbo
    Shi, Kuikui
    Yang, Tao
    Li, Yuquan
    Zhang, Enze
    Zhang, Chuansheng
    Shao, Guangqi
    Shi, Zhen
    Zhang, Chaohai
    CELLULOSE, 2021, 28 (03) : 1703 - 1714
  • [32] Lifespan Model of the Relationships between Ethanol Indicator and Degree of Polymerization of Transformer Paper Insulation
    Zhang, Enze
    Zheng, Hanbo
    Zhang, Yiyi
    Liu, Jiefeng
    Shi, Zhen
    Shi, Kuikui
    Zhang, Chuansheng
    Shao, Guangqi
    Zhang, Chaohai
    Schwarz, Harald
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (06) : 1859 - 1866
  • [33] Extracting Frequency Spectroscopy of Oil-Immersed Paper Based on Havriliak-Negami Model Without Known Insulation Structure of Transformer
    Xu, Qingchuan
    Wang, Shengkang
    Lin, Fuchang
    Li, Hua
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2022, 71
  • [34] Application of Cole-Cole model to transformer oil-paper insulation considering distributed dielectric relaxation
    Ojha, Sandip Kumar
    Purkait, Prithwiraj
    Chatterjee, Biswendu
    Chakravorti, Sivaji
    HIGH VOLTAGE, 2019, 4 (01): : 72 - 79
  • [35] Damage assessment of transformer Kraft paper insulation aged in mineral and vegetable oils
    Fernandez-Diego, C.
    Ortiz, A.
    Carrascal, I. A.
    Fernandez, I.
    Renedo, C. J.
    Delgado, F.
    Diego, S.
    CELLULOSE, 2019, 26 (04) : 2653 - 2672
  • [36] Investigation on Formation Mechanisms of Methanol During Cellulose Insulation Aging Based on Molecular Dynamics Simulation
    Liu, Jiefeng
    Zhao, Huan
    Fan, Xianhao
    Zhang, Yiyi
    IEEE ACCESS, 2021, 9 : 6890 - 6898
  • [37] Study on the influence of preload on the thermal aging of transformer oil-paper insulation
    Liu J.
    Wang F.-Y.
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2020, 24 (06): : 127 - 134
  • [38] A BPNN Model-Based AdaBoost Algorithm for Estimating Inside Moisture of Oil-Paper Insulation of Power Transformer
    Liu, Jiefeng
    Ding, Zheshi
    Fan, Xianhao
    Geng, Chuhan
    Song, Boshu
    Wang, Qingyin
    Zhang, Yiyi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (02) : 614 - 622
  • [39] A comparative study of thermal aging of transformer insulation paper impregnated in natural ester and in mineral oil
    Liao, Ruijin
    Liang, Shuaiwei
    Sun, Caixin
    Yang, Lijun
    Sun, Huigang
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2010, 20 (04): : 518 - 533
  • [40] FDS Measurement-Based Moisture Estimation Model for Transformer Oil-Paper Insulation Including the Aging Effect
    Fan, Xianhao
    Liu, Jiefeng
    Lai, Benghui
    Zhang, Yiyi
    Zhang, Chaohai
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2021, 70