Performance investigation of a combined solar thermal heat pump heating system

被引:68
作者
Li, Hong [1 ]
Sun, Liangliang [2 ]
Zhang, Yonggui [1 ]
机构
[1] Yanshan Univ, Sch Civil Engn & Mech, Qinhuangdao, Hebei, Peoples R China
[2] Southwest Jiaotong Univ, Sch Mech Engn, Chengdu, Sichuan, Peoples R China
关键词
Heat pump; Solar energy; Heating system; TRNSYS; DOMESTIC HOT-WATER; TRNSYS;
D O I
10.1016/j.applthermaleng.2014.07.012
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, a combined solar thermal heat pump system with seasonal energy storage was proposed for both space heating and domestic hot water (DHW) in cold climate area. Using the TRNSYS software, the proposed system was modeled and compared with a conventional space heating system. Moreover, the influence of major parameters on system performance was analyzed. The investigation results show that the average COP of the total system reaches 3.7 during heating months. On average, the monthly COP for space heating is about 3.2. Compared with the traditional space heating system, the system performance is improved obviously and the monthly energy saving ratio for space heating is about 52%. It is also found that the most appropriate dead-band temperature of the air-to-water heat pump unit is 7 degrees C, the optimum storage factor should be within the range of 0.5 m(3)/m(2) to 0.8 m(3)/m(2) and the solar collector area is proposed to be in the range of 130 m(2)-160 m(2). With the specifically proposed parameters, the system performance for space heating is improved by 12.8% compared with the original design. It is concluded that the properly designed solar thermal heat pump heating system can operate effectively and reduce tremendous energy consumption compared with the traditional heating system used in cold climate buildings. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:460 / 468
页数:9
相关论文
共 21 条
  • [11] [韩宗伟 Han Zongwei], 2012, [太阳能学报, Acta Energiae Solaris Sinica], V33, P1411
  • [12] Solar water heating systems and their market trends
    Islam, M. Raisul
    Sumathy, K.
    Khan, Samee Ullah
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 17 : 1 - 25
  • [13] Experimental and theoretical investigation of a solar heating system with heat pump
    Kaygusuz, K
    [J]. RENEWABLE ENERGY, 2000, 21 (01) : 79 - 102
  • [14] Evaluation of combined solar thermal heat pump systems using dynamic system simulations
    Lerch, Werner
    Heinz, Andreas
    Heimrath, Richard
    [J]. PROCEEDINGS OF THE 2ND INTERNATIONAL CONFERENCE ON SOLAR HEATING AND COOLING FOR BUILDINGS AND INDUSTRY (SHC 2013), 2014, 48 : 598 - 607
  • [15] Li Y, 2009, GLOBECOM 2009, P1, DOI [10.1109/GLOCOM.2009.5425547, DOI 10.1109/GLOCOM.2009.5425547]
  • [16] Li Yuanzhe, 2006, CHINA CONSTR HEAT RE, V9, P36
  • [17] Li Yuanzhe, 2012, J HV AC, V42, P62
  • [18] Study on the performance of a solar assisted air source heat pump system for building heating
    Liang, Cai-hua
    Zhang, Xiao-song
    Li, Xiu-wei
    Zhu, Xia
    [J]. ENERGY AND BUILDINGS, 2011, 43 (09) : 2188 - 2196
  • [19] Experimental Investigation on a Solar Air Heat Pump by Heat Source
    Liu, Yin
    Zhou, Guanghui
    Ma, Jing
    [J]. 2011 2ND INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY ENGINEERING (ICAEE), 2012, 14 : 1590 - 1594
  • [20] Feasibility analysis of an indirect heat pump assisted solar domestic hot water system
    Sterling, S. J.
    Collins, M. R.